EA-180GD4-C01 C
29.50 kW
Defrost: None
Product code: EA-263GC10-C08 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 34,362 m³/h |
|---|---|
| Air throw | 43 m |
| External surface | 105.5 m² |
| Inner volume | 43.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 253 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 3,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 72.0 dB(A) |
|---|---|
| Sound power | 95.0 dB(A) |
| Energy class | E |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-263GC10-C08 C | None |
|---|---|
| EA-263GC10-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.27 | 10.96 | 10.77 | 10.66 | 10.54 | 10.42 | 10.30 | 10.27 | 10.86 | 11.71 | 11.41 | 11.30 | 11.14 | 10.91 |
| 5 | 15.24 | 14.97 | 14.80 | 14.71 | 14.56 | 14.38 | 14.20 | 14.14 | 14.94 | 16.09 | 15.62 | 15.44 | 15.19 | 14.82 |
| 6 | 19.33 | 19.19 | 19.12 | 19.08 | 18.97 | 18.79 | 18.57 | 18.46 | 19.50 | 20.99 | 20.33 | 20.09 | 19.75 | 19.23 |
| 7 | 23.29 | 23.39 | 23.52 | 23.66 | 23.64 | 23.50 | 23.27 | 23.15 | 24.46 | 26.33 | 25.49 | 25.18 | 24.73 | 24.03 |
| 8 | 27.08 | 27.50 | 27.90 | 28.20 | 28.34 | 28.31 | 28.16 | 28.06 | 29.67 | 31.97 | 30.98 | 30.60 | 30.04 | 29.17 |
| 9 | 30.61 | 31.28 | 32.05 | 32.74 | 33.10 | 33.22 | 33.17 | 33.14 | 35.06 | 37.84 | 36.73 | 36.30 | 35.65 | 34.61 |
| 10 | 33.59 | 34.71 | 35.77 | 36.75 | 37.40 | 37.82 | 38.05 | 38.27 | 40.54 | 43.83 | 42.64 | 42.15 | 41.44 | 40.25 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.10 | 9.82 | 9.66 | 9.58 | 9.49 | 9.41 | 9.33 | 9.32 | 9.86 | 10.65 | 10.39 | 10.30 | 10.17 | 9.98 |
| 5 | 13.58 | 13.30 | 13.14 | 13.06 | 12.95 | 12.82 | 12.68 | 12.64 | 13.37 | 14.42 | 14.03 | 13.89 | 13.68 | 13.37 |
| 6 | 17.20 | 16.95 | 16.85 | 16.83 | 16.73 | 16.58 | 16.40 | 16.33 | 17.26 | 18.60 | 18.05 | 17.85 | 17.57 | 17.13 |
| 7 | 20.74 | 20.68 | 20.71 | 20.77 | 20.71 | 20.59 | 20.40 | 20.32 | 21.47 | 23.14 | 22.44 | 22.18 | 21.80 | 21.22 |
| 8 | 24.19 | 24.35 | 24.56 | 24.79 | 24.84 | 24.78 | 24.59 | 24.52 | 25.92 | 27.95 | 27.08 | 26.76 | 26.30 | 25.54 |
| 9 | 27.48 | 27.93 | 28.38 | 28.74 | 28.95 | 28.99 | 28.88 | 28.85 | 30.51 | 32.90 | 31.94 | 31.57 | 31.00 | 30.10 |
| 10 | 30.57 | 31.24 | 32.00 | 32.70 | 33.09 | 33.26 | 33.24 | 33.23 | 35.18 | 38.01 | 36.97 | 36.53 | 35.89 | 34.84 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 42.636 | 36.969 |
| SC2 | 0 | 8 | 28.063 | 24.522 |
| SC3 | -18 | 7 | 23.667 | 20.767 |
| SC4 | -25 | 6 | 19.122 | 16.852 |
| SC5 | -34 | 6 | 19.324 | 17.170 |
| A | 3015 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 935 mm |
| E1 | 1318 mm |
| E | 2635 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 3015 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.