EA-263GC10-C08 C
29.47 kW
Defrost: None
Product code: EA-445AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 20,131 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 73.3 m² |
| Inner volume | 34.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 166 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-445AE10-C01 C | None |
|---|---|
| EA-445AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.72 | 10.73 | 10.75 | 10.78 | 10.73 | 10.61 | 10.46 | 10.64 | 11.26 | 12.13 | 11.77 | 11.64 | 11.45 | 11.17 |
| 5 | 14.14 | 14.40 | 14.64 | 14.85 | 14.91 | 14.85 | 14.70 | 14.88 | 15.79 | 17.06 | 16.57 | 16.41 | 16.17 | 15.83 |
| 6 | 17.49 | 18.05 | 18.57 | 19.03 | 19.23 | 19.30 | 19.21 | 19.42 | 20.59 | 22.27 | 21.60 | 21.36 | 20.99 | 20.43 |
| 7 | 20.48 | 21.38 | 22.22 | 22.99 | 23.51 | 23.83 | 23.86 | 24.06 | 25.54 | 27.68 | 26.91 | 26.60 | 26.14 | 25.37 |
| 8 | 23.05 | 24.31 | 25.48 | 26.41 | 27.15 | 27.63 | 27.88 | 28.30 | 30.09 | 32.73 | 32.01 | 31.70 | 31.23 | 30.45 |
| 9 | 25.43 | 27.09 | 28.45 | 29.82 | 30.81 | 31.47 | 31.85 | 32.36 | 34.41 | 37.42 | 36.64 | 36.28 | 35.74 | 34.81 |
| 10 | 27.59 | 29.50 | 31.41 | 33.13 | 34.37 | 35.25 | 35.79 | 36.42 | 38.74 | 42.15 | 41.31 | 40.91 | 40.30 | 39.22 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 41.312 |
| SC2 | 0 | 8 | 28.302 |
| SC3 | -18 | 7 | 23.226 |
| SC4 | -25 | 6 | 18.574 |
| SC5 | -34 | 6 | 17.631 |
| A | 3167 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.