EA-330AE10-C05 C
6.31 kW
Defrost: None
Product code: EA-330AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,991 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 20.7 m² |
| Inner volume | 7.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AC7-C01 C | None |
|---|---|
| EA-330AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.34 | 2.31 | 2.29 | 2.29 | 2.28 | 2.26 | 2.24 | 2.28 | 2.41 | 2.61 | 2.55 | 2.53 | 2.50 | 2.45 |
| 5 | 3.12 | 3.12 | 3.12 | 3.14 | 3.13 | 3.11 | 3.07 | 3.11 | 3.30 | 3.57 | 3.48 | 3.45 | 3.40 | 3.34 |
| 6 | 3.90 | 3.94 | 3.99 | 4.03 | 4.04 | 4.03 | 4.00 | 4.03 | 4.27 | 4.61 | 4.47 | 4.43 | 4.36 | 4.26 |
| 7 | 4.67 | 4.77 | 4.87 | 4.95 | 4.99 | 5.00 | 4.97 | 5.00 | 5.30 | 5.73 | 5.55 | 5.48 | 5.39 | 5.23 |
| 8 | 5.38 | 5.55 | 5.72 | 5.87 | 5.96 | 5.99 | 5.98 | 6.01 | 6.37 | 6.90 | 6.69 | 6.61 | 6.49 | 6.30 |
| 9 | 6.00 | 6.24 | 6.46 | 6.67 | 6.82 | 6.89 | 6.93 | 7.01 | 7.44 | 8.08 | 7.86 | 7.76 | 7.63 | 7.40 |
| 10 | 6.57 | 6.89 | 7.19 | 7.43 | 7.62 | 7.74 | 7.80 | 7.90 | 8.39 | 9.11 | 8.91 | 8.82 | 8.69 | 8.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.910 |
| SC2 | 0 | 8 | 6.013 |
| SC3 | -18 | 7 | 4.969 |
| SC4 | -25 | 6 | 3.986 |
| SC5 | -34 | 6 | 3.912 |
| A | 1657 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 451 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.