EA-330AE10-C05 C
6.31 kW
Defrost: None
Product code: EA-145AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,338 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 16.7 m² |
| Inner volume | 5.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 45 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-145AC7-C01 C | None |
|---|---|
| EA-145AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.21 | 2.21 | 2.22 | 2.22 | 2.20 | 2.18 | 2.15 | 2.17 | 2.29 | 2.46 | 2.39 | 2.36 | 2.32 | 2.27 |
| 5 | 2.95 | 3.02 | 3.07 | 3.12 | 3.12 | 3.11 | 3.07 | 3.10 | 3.28 | 3.54 | 3.44 | 3.40 | 3.35 | 3.26 |
| 6 | 3.67 | 3.82 | 3.95 | 4.06 | 4.11 | 4.11 | 4.09 | 4.13 | 4.38 | 4.73 | 4.58 | 4.53 | 4.46 | 4.35 |
| 7 | 4.29 | 4.51 | 4.71 | 4.89 | 5.01 | 5.06 | 5.10 | 5.18 | 5.51 | 5.98 | 5.81 | 5.75 | 5.65 | 5.50 |
| 8 | 4.82 | 5.13 | 5.37 | 5.62 | 5.80 | 5.91 | 5.97 | 6.06 | 6.45 | 7.01 | 6.87 | 6.81 | 6.72 | 6.57 |
| 9 | 5.30 | 5.67 | 6.03 | 6.35 | 6.59 | 6.75 | 6.85 | 6.96 | 7.40 | 8.06 | 7.90 | 7.83 | 7.73 | 7.55 |
| 10 | 5.74 | 6.20 | 6.65 | 7.06 | 7.37 | 7.58 | 7.72 | 7.86 | 8.37 | 9.11 | 8.94 | 8.87 | 8.75 | 8.55 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.942 |
| SC2 | 0 | 8 | 6.064 |
| SC3 | -18 | 7 | 4.945 |
| SC4 | -25 | 6 | 3.951 |
| SC5 | -34 | 6 | 3.709 |
| A | 1067 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E | 735 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1067 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.