EA-430AE8-C05 C
8.63 kW
Defrost: None
Product code: EA-330AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,309 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 49.5 m² |
| Inner volume | 10.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 59 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.8 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AE4-C01 C | None |
|---|---|
| EA-330AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.43 | 3.45 | 3.48 | 3.53 | 3.54 | 3.54 | 3.52 | 3.62 | 3.86 | 4.20 | 4.12 | 4.10 | 4.07 | 4.03 |
| 5 | 4.38 | 4.46 | 4.54 | 4.62 | 4.66 | 4.66 | 4.63 | 4.71 | 5.01 | 5.44 | 5.30 | 5.25 | 5.18 | 5.08 |
| 6 | 5.33 | 5.48 | 5.61 | 5.74 | 5.81 | 5.83 | 5.80 | 5.87 | 6.23 | 6.75 | 6.55 | 6.47 | 6.35 | 6.15 |
| 7 | 6.20 | 6.44 | 6.67 | 6.87 | 6.99 | 7.02 | 7.00 | 7.07 | 7.50 | 8.12 | 7.85 | 7.74 | 7.57 | 7.29 |
| 8 | 6.99 | 7.33 | 7.65 | 7.93 | 8.11 | 8.20 | 8.21 | 8.29 | 8.78 | 9.49 | 9.19 | 9.05 | 8.84 | 8.48 |
| 9 | 7.69 | 8.14 | 8.56 | 8.88 | 9.13 | 9.26 | 9.31 | 9.42 | 9.99 | 10.82 | 10.51 | 10.36 | 10.14 | 9.71 |
| 10 | 8.34 | 8.91 | 9.38 | 9.84 | 10.15 | 10.34 | 10.42 | 10.54 | 11.18 | 12.09 | 11.76 | 11.59 | 11.33 | 10.88 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.758 |
| SC2 | 0 | 8 | 8.290 |
| SC3 | -18 | 7 | 6.929 |
| SC4 | -25 | 6 | 5.607 |
| SC5 | -34 | 6 | 5.368 |
| A | 1657 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 451 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.