EA-530AC8-C05 C
8.60 kW
Defrost: None
Product code: EA-335AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,669 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 20.9 m² |
| Inner volume | 9.8 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 65 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-335AC10-C01 C | None |
|---|---|
| EA-335AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.06 | 3.09 | 3.13 | 3.16 | 3.16 | 3.14 | 3.11 | 3.15 | 3.33 | 3.58 | 3.48 | 3.44 | 3.39 | 3.30 |
| 5 | 3.99 | 4.12 | 4.23 | 4.33 | 4.38 | 4.40 | 4.38 | 4.43 | 4.70 | 5.08 | 4.94 | 4.90 | 4.83 | 4.73 |
| 6 | 4.90 | 5.13 | 5.34 | 5.53 | 5.64 | 5.70 | 5.72 | 5.78 | 6.14 | 6.66 | 6.49 | 6.43 | 6.33 | 6.17 |
| 7 | 5.67 | 6.00 | 6.31 | 6.58 | 6.75 | 6.89 | 6.98 | 7.10 | 7.56 | 8.23 | 8.08 | 8.02 | 7.91 | 7.72 |
| 8 | 6.35 | 6.79 | 7.15 | 7.52 | 7.80 | 7.99 | 8.12 | 8.27 | 8.81 | 9.60 | 9.44 | 9.37 | 9.26 | 9.08 |
| 9 | 6.96 | 7.47 | 7.99 | 8.46 | 8.82 | 9.09 | 9.27 | 9.45 | 10.07 | 10.98 | 10.81 | 10.73 | 10.61 | 10.39 |
| 10 | ≈ 7.51 | 8.14 | 8.78 | 9.37 | 9.82 | 10.16 | 10.40 | 10.63 | 11.33 | 12.36 | 12.19 | 12.10 | 11.97 | 11.72 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.188 |
| SC2 | 0 | 8 | 8.272 |
| SC3 | -18 | 7 | 6.669 |
| SC4 | -25 | 6 | 5.340 |
| SC5 | -34 | 6 | 4.952 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.