EA-163EE7-C11 C
17.72 kW
Defrost: None
Product code: EA-340AE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,775 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 87.6 m² |
| Inner volume | 18.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 101 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-340AE4-C01 C | None |
|---|---|
| EA-340AE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.86 | 6.83 | 6.84 | 6.86 | 6.85 | 6.81 | 6.75 | 6.96 | 7.44 | 8.08 | 7.95 | 7.92 | 7.84 | 7.73 |
| 5 | 8.98 | 9.05 | 9.13 | 9.22 | 9.22 | 9.17 | 9.06 | 9.25 | 9.84 | 10.66 | 10.39 | 10.30 | 10.19 | 10.04 |
| 6 | 11.11 | 11.33 | 11.50 | 11.69 | 11.75 | 11.70 | 11.57 | 11.72 | 12.43 | 13.45 | 13.02 | 12.87 | 12.65 | 12.31 |
| 7 | 13.09 | 13.52 | 13.90 | 14.22 | 14.37 | 14.36 | 14.22 | 14.34 | 15.19 | 16.43 | 15.86 | 15.64 | 15.31 | 14.80 |
| 8 | 14.82 | 15.43 | 15.99 | 16.48 | 16.77 | 16.86 | 16.84 | 17.04 | 18.05 | 19.50 | 18.83 | 18.55 | 18.14 | 17.46 |
| 9 | 16.41 | 17.24 | 17.91 | 18.57 | 18.99 | 19.18 | 19.20 | 19.41 | 20.58 | 22.28 | 21.66 | 21.37 | 20.94 | 20.21 |
| 10 | 17.89 | 18.87 | 19.84 | 20.68 | 21.21 | 21.51 | 21.58 | 21.82 | 23.13 | 25.03 | 24.33 | 24.00 | 23.50 | 22.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.330 |
| SC2 | 0 | 8 | 17.035 |
| SC3 | -18 | 7 | 14.296 |
| SC4 | -25 | 6 | 11.500 |
| SC5 | -34 | 6 | 11.172 |
| A | 2017 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2017 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.