EA-163GD10-C08 C
17.80 kW
Defrost: None
Product code: EA-340AG7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,715 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 73.4 m² |
| Inner volume | 24.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 119 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-340AG7-C01 C | None |
|---|---|
| EA-340AG7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.17 | 7.06 | 7.02 | 7.02 | 6.98 | 6.92 | 6.84 | 7.06 | 7.53 | 8.18 | 8.04 | 8.00 | 7.93 | 7.81 |
| 5 | 9.44 | 9.38 | 9.38 | 9.40 | 9.37 | 9.29 | 9.16 | 9.34 | 9.92 | 10.76 | 10.46 | 10.37 | 10.24 | 10.08 |
| 6 | 11.70 | 11.74 | 11.81 | 11.90 | 11.90 | 11.81 | 11.65 | 11.78 | 12.49 | 13.51 | 13.06 | 12.90 | 12.67 | 12.32 |
| 7 | 13.91 | 14.07 | 14.27 | 14.45 | 14.50 | 14.44 | 14.26 | 14.36 | 15.19 | 16.42 | 15.83 | 15.60 | 15.26 | 14.71 |
| 8 | 16.10 | 16.42 | 16.74 | 17.01 | 17.14 | 17.12 | 16.94 | 17.03 | 18.00 | 19.42 | 18.73 | 18.43 | 18.00 | 17.27 |
| 9 | 18.12 | 18.64 | 19.14 | 19.58 | 19.79 | 19.80 | 19.66 | 19.75 | 20.88 | 22.51 | 21.73 | 21.38 | 20.85 | 19.97 |
| 10 | 19.95 | 20.67 | 21.36 | 21.98 | 22.34 | 22.50 | 22.41 | 22.51 | 23.80 | 25.66 | 24.79 | 24.39 | 23.77 | 22.73 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.791 |
| SC2 | 0 | 8 | 17.025 |
| SC3 | -18 | 7 | 14.485 |
| SC4 | -25 | 6 | 11.812 |
| SC5 | -34 | 6 | 11.722 |
| A | 2017 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2017 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.