EA-440AC8-C01 C
15.42 kW
Defrost: None
Product code: EA-340AE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,792 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 48.6 m² |
| Inner volume | 17.8 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 96 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-340AE8-C01 C | None |
|---|---|
| EA-340AE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.71 | 5.73 | 5.76 | 5.79 | 5.78 | 5.73 | 5.66 | 5.80 | 6.18 | 6.67 | 6.50 | 6.43 | 6.34 | 6.20 |
| 5 | 7.47 | 7.63 | 7.77 | 7.89 | 7.93 | 7.90 | 7.82 | 7.96 | 8.46 | 9.16 | 8.90 | 8.82 | 8.70 | 8.54 |
| 6 | 9.21 | 9.52 | 9.81 | 10.06 | 10.16 | 10.19 | 10.13 | 10.26 | 10.89 | 11.78 | 11.42 | 11.28 | 11.08 | 10.77 |
| 7 | 10.77 | 11.26 | 11.72 | 12.13 | 12.40 | 12.53 | 12.51 | 12.66 | 13.40 | 14.52 | 14.08 | 13.91 | 13.64 | 13.21 |
| 8 | 12.10 | 12.79 | 13.42 | 13.91 | 14.30 | 14.53 | 14.62 | 14.85 | 15.77 | 17.14 | 16.73 | 16.54 | 16.27 | 15.76 |
| 9 | 13.32 | 14.23 | 14.96 | 15.69 | 16.19 | 16.51 | 16.67 | 16.94 | 18.00 | 19.55 | 19.10 | 18.89 | 18.57 | 18.03 |
| 10 | 14.44 | 15.47 | 16.50 | 17.40 | 18.06 | 18.49 | 18.72 | 19.04 | 20.24 | 21.99 | 21.50 | 21.27 | 20.90 | 20.27 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.501 |
| SC2 | 0 | 8 | 14.845 |
| SC3 | -18 | 7 | 12.256 |
| SC4 | -25 | 6 | 9.813 |
| SC5 | -34 | 6 | 9.286 |
| A | 2017 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.