EA-340AE8-C01 C
15.42 kW
Defrost: None
Product code: EA-440AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,127 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 43.5 m² |
| Inner volume | 16.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 103 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-440AC8-C01 C | None |
|---|---|
| EA-440AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.50 | 5.55 | 5.60 | 5.64 | 5.64 | 5.60 | 5.54 | 5.60 | 5.92 | 6.38 | 6.20 | 6.13 | 6.04 | 5.89 |
| 5 | 7.21 | 7.43 | 7.62 | 7.78 | 7.86 | 7.86 | 7.82 | 7.90 | 8.39 | 9.07 | 8.82 | 8.74 | 8.61 | 8.43 |
| 6 | 8.88 | 9.29 | 9.66 | 9.98 | 10.17 | 10.26 | 10.25 | 10.37 | 11.01 | 11.92 | 11.61 | 11.49 | 11.30 | 11.03 |
| 7 | 10.27 | 10.84 | 11.38 | 11.86 | 12.14 | 12.37 | 12.50 | 12.71 | 13.52 | 14.72 | 14.43 | 14.32 | 14.16 | 13.85 |
| 8 | 11.50 | 12.29 | 12.92 | 13.57 | 14.04 | 14.37 | 14.58 | 14.83 | 15.79 | 17.19 | 16.88 | 16.75 | 16.55 | 16.22 |
| 9 | 12.62 | 13.53 | 14.45 | 15.29 | 15.91 | 16.36 | 16.65 | 16.96 | 18.07 | 19.69 | 19.36 | 19.21 | 18.98 | 18.59 |
| 10 | ≈ 13.43 | 14.76 | 15.90 | 16.94 | 17.74 | 18.32 | 18.71 | 19.10 | 20.35 | 22.20 | 21.86 | 21.69 | 21.44 | 21.00 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.856 |
| SC2 | 0 | 8 | 14.830 |
| SC3 | -18 | 7 | 11.949 |
| SC4 | -25 | 6 | 9.657 |
| SC5 | -34 | 6 | 8.975 |
| A | 2567 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2567 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.