EA-245AE4-C01 C
18.64 kW
Defrost: None
Product code: EA-340AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,500 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 84.4 m² |
| Inner volume | 24.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 123 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-340AG6-C01 C | None |
|---|---|
| EA-340AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.63 | 7.55 | 7.53 | 7.55 | 7.53 | 7.48 | 7.41 | 7.64 | 8.16 | 8.87 | 8.72 | 8.68 | 8.63 | 8.56 |
| 5 | 9.95 | 9.93 | 9.96 | 10.02 | 10.01 | 9.94 | 9.82 | 10.01 | 10.65 | 11.55 | 11.24 | 11.14 | 11.00 | 10.80 |
| 6 | 12.25 | 12.33 | 12.45 | 12.58 | 12.60 | 12.54 | 12.39 | 12.54 | 13.29 | 14.39 | 13.92 | 13.75 | 13.50 | 13.11 |
| 7 | 14.54 | 14.71 | 14.95 | 15.18 | 15.27 | 15.22 | 15.06 | 15.17 | 16.06 | 17.37 | 16.75 | 16.51 | 16.15 | 15.56 |
| 8 | 16.68 | 17.08 | 17.46 | 17.82 | 17.96 | 17.94 | 17.79 | 17.89 | 18.92 | 20.42 | 19.71 | 19.40 | 18.94 | 18.18 |
| 9 | 18.71 | 19.31 | 19.89 | 20.40 | 20.67 | 20.71 | 20.56 | 20.67 | 21.85 | 23.57 | 22.76 | 22.39 | 21.84 | 20.91 |
| 10 | 20.52 | 21.33 | 22.09 | 22.77 | 23.17 | 23.36 | 23.33 | 23.45 | 24.80 | 26.72 | 25.84 | 25.42 | 24.78 | 23.68 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 25.835 |
| SC2 | 0 | 8 | 17.894 |
| SC3 | -18 | 7 | 15.233 |
| SC4 | -25 | 6 | 12.453 |
| SC5 | -34 | 6 | 12.282 |
| A | 2017 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 2017 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.