EA-340AG6-C01 C
18.66 kW
Defrost: None
Product code: EA-540AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,777 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 44.6 m² |
| Inner volume | 19.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 124 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-540AC10-C01 C | None |
|---|---|
| EA-540AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.72 | 6.73 | 6.75 | 6.77 | 6.74 | 6.68 | 6.59 | 6.64 | 7.01 | 7.55 | 7.32 | 7.23 | 7.11 | 6.92 |
| 5 | 8.88 | 9.07 | 9.24 | 9.39 | 9.44 | 9.42 | 9.35 | 9.43 | 9.99 | 10.79 | 10.48 | 10.37 | 10.21 | 9.98 |
| 6 | 10.99 | 11.39 | 11.75 | 12.07 | 12.25 | 12.31 | 12.30 | 12.41 | 13.16 | 14.24 | 13.84 | 13.69 | 13.47 | 13.13 |
| 7 | 12.82 | 13.42 | 13.98 | 14.50 | 14.86 | 15.05 | 15.19 | 15.42 | 16.40 | 17.81 | 17.37 | 17.20 | 16.94 | 16.52 |
| 8 | 14.42 | 15.26 | 15.95 | 16.65 | 17.16 | 17.51 | 17.73 | 18.01 | 19.17 | 20.87 | 20.48 | 20.32 | 20.07 | 19.66 |
| 9 | 15.89 | 16.89 | 17.89 | 18.80 | 19.48 | 19.96 | 20.28 | 20.62 | 21.95 | 23.91 | 23.50 | 23.32 | 23.04 | 22.56 |
| 10 | 17.23 | 18.48 | 19.74 | 20.89 | 21.75 | 22.38 | 22.81 | 23.23 | 24.75 | 26.97 | 26.54 | 26.34 | 26.03 | 25.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.542 |
| SC2 | 0 | 8 | 18.014 |
| SC3 | -18 | 7 | 14.660 |
| SC4 | -25 | 6 | 11.752 |
| SC5 | -34 | 6 | 11.093 |
| A | 3117 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 3117 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.