EA-250AC6-C09 C
17.80 kW
Defrost: None
Product code: EA-435AG8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,040 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 67.8 m² |
| Inner volume | 25.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 124 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-435AG8-C01 C | None |
|---|---|
| EA-435AG8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.98 | 6.94 | 6.93 | 6.95 | 6.93 | 6.88 | 6.80 | 6.98 | 7.45 | 8.08 | 7.92 | 7.88 | 7.80 | 7.67 |
| 5 | 9.12 | 9.17 | 9.24 | 9.32 | 9.33 | 9.27 | 9.16 | 9.33 | 9.91 | 10.73 | 10.43 | 10.33 | 10.20 | 10.01 |
| 6 | 11.21 | 11.39 | 11.58 | 11.76 | 11.83 | 11.80 | 11.68 | 11.81 | 12.53 | 13.55 | 13.12 | 12.95 | 12.71 | 12.33 |
| 7 | 13.27 | 13.62 | 13.95 | 14.22 | 14.37 | 14.39 | 14.29 | 14.41 | 15.26 | 16.51 | 15.94 | 15.71 | 15.36 | 14.79 |
| 8 | 15.16 | 15.71 | 16.23 | 16.68 | 16.94 | 16.99 | 16.93 | 17.07 | 18.07 | 19.53 | 18.87 | 18.59 | 18.16 | 17.44 |
| 9 | 16.88 | 17.63 | 18.33 | 18.97 | 19.36 | 19.57 | 19.60 | 19.74 | 20.89 | 22.57 | 21.85 | 21.51 | 21.01 | 20.14 |
| 10 | 18.43 | 19.41 | 20.32 | 21.13 | 21.56 | 21.87 | 21.98 | 22.24 | 23.58 | 25.52 | 24.82 | 24.48 | 23.91 | 22.90 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.821 |
| SC2 | 0 | 8 | 17.067 |
| SC3 | -18 | 7 | 14.295 |
| SC4 | -25 | 6 | 11.584 |
| SC5 | -34 | 6 | 11.261 |
| A | 2357 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2357 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.