EA-163EC4-C11 C
16.55 kW
Defrost: None
Product code: EA-345AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 16,651 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 36.3 m² |
| Inner volume | 16.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 106 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-345AC10-C01 C | None |
|---|---|
| EA-345AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.81 | 5.87 | 5.92 | 5.96 | 5.94 | 5.88 | 5.79 | 5.82 | 6.14 | 6.59 | 6.37 | 6.29 | 6.17 | 5.99 |
| 5 | 7.70 | 7.94 | 8.13 | 8.31 | 8.39 | 8.40 | 8.34 | 8.41 | 8.92 | 9.62 | 9.34 | 9.23 | 9.08 | 8.86 |
| 6 | 9.41 | 9.85 | 10.26 | 10.62 | 10.88 | 11.03 | 11.06 | 11.13 | 11.82 | 12.80 | 12.46 | 12.33 | 12.14 | 11.84 |
| 7 | 10.81 | 11.46 | 12.06 | 12.52 | 12.90 | 13.16 | 13.32 | 13.54 | 14.41 | 15.68 | 15.39 | 15.28 | 15.10 | 14.81 |
| 8 | 12.10 | 12.88 | 13.68 | 14.40 | 14.93 | 15.31 | 15.55 | 15.83 | 16.86 | 18.37 | 18.05 | 17.91 | 17.70 | 17.35 |
| 9 | 13.09 | 14.27 | 15.29 | 16.22 | 16.92 | 17.43 | 17.78 | 18.13 | 19.32 | 21.07 | 20.73 | 20.58 | 20.34 | 19.93 |
| 10 | ≈ 14.22 | 15.55 | 16.81 | 17.96 | 18.86 | 19.52 | 19.99 | 20.43 | 21.78 | 23.77 | 23.43 | 23.26 | 23.01 | 22.54 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.429 |
| SC2 | 0 | 8 | 15.832 |
| SC3 | -18 | 7 | 12.686 |
| SC4 | -25 | 6 | 10.256 |
| SC5 | -34 | 6 | 9.513 |
| A | 2467 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2135 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2467 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.