EA-350AG6-C09 C
39.94 kW
Defrost: None
Product code: EA-363ED4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 23,575 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 250.1 m² |
| Inner volume | 49.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 296 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 79.5 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363ED4-C01 C | None |
|---|---|
| EA-363ED4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 15.40 | 15.48 | 15.61 | 15.75 | 15.79 | 15.76 | 15.69 | 16.05 | 17.10 | 18.53 | 18.18 | 18.04 | 17.86 | 17.58 |
| 5 | 19.99 | 20.37 | 20.71 | 21.02 | 21.14 | 21.10 | 20.97 | 21.31 | 22.65 | 24.55 | 23.99 | 23.81 | 23.54 | 23.14 |
| 6 | 24.31 | 25.15 | 25.75 | 26.36 | 26.68 | 26.76 | 26.65 | 26.96 | 28.61 | 30.98 | 30.15 | 29.85 | 29.42 | 28.77 |
| 7 | 28.13 | 29.40 | 30.55 | 31.58 | 32.25 | 32.62 | 32.60 | 32.93 | 34.93 | 37.83 | 36.78 | 36.37 | 35.77 | 34.82 |
| 8 | 31.49 | 33.25 | 34.85 | 36.25 | 37.19 | 37.74 | 37.98 | 38.47 | 40.87 | 44.39 | 43.36 | 42.94 | 42.32 | 41.21 |
| 9 | 34.57 | 36.88 | 38.99 | 40.82 | 42.08 | 42.86 | 43.24 | 43.79 | 46.52 | 50.52 | 49.35 | 48.85 | 48.10 | 46.84 |
| 10 | 37.38 | 40.28 | 42.94 | 45.26 | 46.87 | 47.92 | 48.47 | 49.15 | 52.22 | 56.71 | 55.43 | 54.85 | 53.98 | 52.50 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 55.427 |
| SC2 | 0 | 8 | 38.472 |
| SC3 | -18 | 7 | 31.888 |
| SC4 | -25 | 6 | 25.747 |
| SC5 | -34 | 6 | 24.527 |
| A | 2815 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.