EA-363EC10-C11 C
33.87 kW
Defrost: None
Product code: EA-363ED7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 25,033 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 168.5 m² |
| Inner volume | 49.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 277 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 79.1 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363ED7-C01 C | None |
|---|---|
| EA-363ED7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.95 | 12.86 | 12.84 | 12.86 | 12.83 | 12.77 | 12.68 | 12.89 | 13.65 | 14.77 | 14.44 | 14.32 | 14.15 | 13.90 |
| 5 | 17.06 | 17.13 | 17.20 | 17.32 | 17.33 | 17.25 | 17.12 | 17.30 | 18.36 | 19.87 | 19.38 | 19.22 | 18.98 | 18.63 |
| 6 | 21.02 | 21.39 | 21.73 | 22.04 | 22.15 | 22.11 | 21.95 | 22.11 | 23.44 | 25.34 | 24.65 | 24.39 | 24.02 | 23.48 |
| 7 | 24.77 | 25.54 | 26.11 | 26.69 | 27.00 | 27.08 | 26.99 | 27.16 | 28.79 | 31.12 | 30.23 | 29.89 | 29.40 | 28.62 |
| 8 | 28.10 | 29.24 | 30.30 | 31.25 | 31.88 | 32.17 | 32.18 | 32.40 | 34.35 | 37.17 | 36.13 | 35.72 | 35.10 | 34.09 |
| 9 | 31.07 | 32.63 | 34.06 | 35.34 | 36.19 | 36.72 | 36.98 | 37.38 | 39.69 | 43.10 | 42.12 | 41.70 | 40.97 | 39.75 |
| 10 | 33.81 | 35.85 | 37.70 | 39.33 | 40.46 | 41.18 | 41.56 | 42.04 | 44.65 | 48.48 | 47.40 | 46.93 | 46.22 | 45.02 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 47.399 |
| SC2 | 0 | 8 | 32.401 |
| SC3 | -18 | 7 | 26.847 |
| SC4 | -25 | 6 | 21.733 |
| SC5 | -34 | 6 | 21.124 |
| A | 2815 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.