EA-550AC10-C10 C
32.41 kW
Defrost: None
Product code: EA-363EE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 24,982 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 146.5 m² |
| Inner volume | 60.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 291 kg |
| Quantity | 3 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 1,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 79.1 dB(A) |
| Energy class | C |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø54 |
| EA-363EE10-C01 C | None |
|---|---|
| EA-363EE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 12.78 | 12.54 | 12.41 | 12.36 | 12.27 | 12.16 | 12.04 | 12.21 | 12.93 | 13.97 | 13.64 | 13.52 | 13.35 | 13.10 |
| 5 | 16.95 | 16.79 | 16.73 | 16.72 | 16.63 | 16.49 | 16.30 | 16.43 | 17.42 | 18.83 | 18.34 | 18.16 | 17.93 | 17.58 |
| 6 | 21.20 | 21.20 | 21.24 | 21.35 | 21.31 | 21.17 | 20.94 | 21.04 | 22.28 | 24.04 | 23.33 | 23.07 | 22.71 | 22.17 |
| 7 | 25.26 | 25.55 | 25.85 | 26.13 | 26.20 | 26.08 | 25.85 | 25.92 | 27.43 | 29.61 | 28.68 | 28.33 | 27.82 | 27.03 |
| 8 | 29.14 | 29.79 | 30.39 | 30.92 | 31.15 | 31.15 | 30.91 | 30.98 | 32.77 | 35.39 | 34.27 | 33.84 | 33.18 | 32.13 |
| 9 | 32.80 | 33.87 | 34.70 | 35.54 | 36.00 | 36.16 | 36.07 | 36.18 | 38.29 | 41.37 | 40.10 | 39.57 | 38.79 | 37.52 |
| 10 | 35.95 | 37.43 | 38.76 | 39.98 | 40.77 | 41.21 | 41.25 | 41.44 | 43.89 | 47.45 | 46.05 | 45.45 | 44.56 | 43.07 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 46.053 |
| SC2 | 0 | 8 | 30.983 |
| SC3 | -18 | 7 | 26.181 |
| SC4 | -25 | 6 | 21.236 |
| SC5 | -34 | 6 | 21.226 |
| A | 2815 mm |
|---|---|
| B | 1000 mm |
| C | 1190 mm |
| F | 960 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø54 |
| Length | 2815 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.