EA-240AC7-C01 C
8.70 kW
Defrost: None
Product code: EA-430AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,340 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 27.8 m² |
| Inner volume | 9.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.1 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-430AC7-C01 C | None |
|---|---|
| EA-430AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.24 | 3.22 | 3.21 | 3.22 | 3.20 | 3.18 | 3.15 | 3.21 | 3.40 | 3.68 | 3.59 | 3.56 | 3.51 | 3.45 |
| 5 | 4.29 | 4.32 | 4.35 | 4.39 | 4.39 | 4.37 | 4.33 | 4.38 | 4.65 | 5.03 | 4.90 | 4.86 | 4.80 | 4.71 |
| 6 | 5.34 | 5.44 | 5.52 | 5.61 | 5.65 | 5.65 | 5.62 | 5.66 | 6.00 | 6.49 | 6.31 | 6.24 | 6.14 | 5.99 |
| 7 | 6.32 | 6.51 | 6.69 | 6.86 | 6.95 | 6.97 | 6.96 | 7.01 | 7.43 | 8.04 | 7.81 | 7.72 | 7.59 | 7.37 |
| 8 | 7.19 | 7.48 | 7.75 | 8.00 | 8.16 | 8.27 | 8.30 | 8.39 | 8.90 | 9.64 | 9.37 | 9.27 | 9.10 | 8.84 |
| 9 | 7.98 | 8.37 | 8.73 | 9.03 | 9.26 | 9.40 | 9.48 | 9.60 | 10.20 | 11.08 | 10.85 | 10.74 | 10.58 | 10.32 |
| 10 | 8.71 | 9.22 | 9.64 | 10.06 | 10.36 | 10.55 | 10.67 | 10.82 | 11.49 | 12.49 | 12.23 | 12.11 | 11.93 | 11.63 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.227 |
| SC2 | 0 | 8 | 8.387 |
| SC3 | -18 | 7 | 6.900 |
| SC4 | -25 | 6 | 5.516 |
| SC5 | -34 | 6 | 5.369 |
| A | 2107 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 455 mm |
| E2 | 438 mm |
| E | 1785 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.