EA-445AC7-C01 C
25.50 kW
Defrost: None
Product code: EA-440AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,996 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 112.5 m² |
| Inner volume | 32.8 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 158 kg |
| Quantity | 4 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 640 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-440AG6-C01 C | None |
|---|---|
| EA-440AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 10.06 | 10.17 | 10.30 | 10.43 | 10.47 | 10.43 | 10.33 | 10.66 | 11.39 | 12.38 | 12.14 | 12.07 | 11.99 | 11.88 |
| 5 | 12.83 | 13.15 | 13.45 | 13.72 | 13.84 | 13.83 | 13.72 | 13.99 | 14.88 | 16.15 | 15.69 | 15.53 | 15.31 | 14.97 |
| 6 | 15.56 | 16.11 | 16.62 | 17.03 | 17.28 | 17.34 | 17.24 | 17.48 | 18.55 | 20.10 | 19.46 | 19.21 | 18.83 | 18.21 |
| 7 | 18.02 | 18.88 | 19.67 | 20.34 | 20.75 | 20.91 | 20.81 | 21.07 | 22.33 | 24.19 | 23.41 | 23.08 | 22.58 | 21.74 |
| 8 | 20.21 | 21.35 | 22.40 | 23.33 | 23.83 | 24.15 | 24.23 | 24.57 | 26.06 | 28.26 | 27.39 | 27.00 | 26.39 | 25.34 |
| 9 | 22.19 | 23.67 | 24.86 | 26.07 | 26.86 | 27.33 | 27.48 | 27.86 | 29.55 | 32.02 | 31.16 | 30.74 | 30.09 | 28.97 |
| 10 | 24.00 | 25.61 | 27.36 | 28.84 | 29.85 | 30.47 | 30.73 | 31.17 | 33.06 | 35.81 | 34.87 | 34.40 | 33.66 | 32.37 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 34.866 |
| SC2 | 0 | 8 | 24.566 |
| SC3 | -18 | 7 | 20.535 |
| SC4 | -25 | 6 | 16.624 |
| SC5 | -34 | 6 | 15.697 |
| A | 2567 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2235 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 2567 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.