EA-440AG6-C01 C
25.47 kW
Defrost: None
Product code: EA-445AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 21,371 m³/h |
|---|---|
| Air throw | 19 m |
| External surface | 66.8 m² |
| Inner volume | 23.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 141 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø54 |
| EA-445AC7-C01 C | None |
|---|---|
| EA-445AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.96 | 8.72 | 8.56 | 8.46 | 8.33 | 8.20 | 8.08 | 8.12 | 8.57 | 9.24 | 8.99 | 8.90 | 8.77 | 8.59 |
| 5 | 12.37 | 12.20 | 12.09 | 12.01 | 11.87 | 11.68 | 11.47 | 11.54 | 12.21 | 13.13 | 12.72 | 12.56 | 12.35 | 12.04 |
| 6 | 15.88 | 15.84 | 15.88 | 15.92 | 15.83 | 15.65 | 15.39 | 15.43 | 16.32 | 17.57 | 16.98 | 16.78 | 16.50 | 16.08 |
| 7 | 19.24 | 19.52 | 19.79 | 20.02 | 20.05 | 19.92 | 19.68 | 19.72 | 20.85 | 22.45 | 21.66 | 21.37 | 20.96 | 20.34 |
| 8 | 22.16 | 22.71 | 23.26 | 23.78 | 24.10 | 24.25 | 24.19 | 24.21 | 25.62 | 27.64 | 26.72 | 26.37 | 25.85 | 25.03 |
| 9 | 24.82 | 25.66 | 26.46 | 27.11 | 27.58 | 27.85 | 27.94 | 28.20 | 29.93 | 32.46 | 31.67 | 31.35 | 30.88 | 30.03 |
| 10 | 27.32 | 28.39 | 29.47 | 30.46 | 31.11 | 31.51 | 31.69 | 31.99 | 33.96 | 36.84 | 35.97 | 35.60 | 35.06 | 34.16 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 35.968 |
| SC2 | 0 | 8 | 24.209 |
| SC3 | -18 | 7 | 20.052 |
| SC4 | -25 | 6 | 15.883 |
| SC5 | -34 | 6 | 15.905 |
| A | 3167 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø54 |
| Length | 3167 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.