EA-163EE7-C01 C
12.20 kW
Defrost: None
Product code: EA-530AC4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,070 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 52.0 m² |
| Inner volume | 11.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 73 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 71.8 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-530AC4-C01 C | None |
|---|---|
| EA-530AC4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.59 | 4.70 | 4.81 | 4.90 | 4.94 | 4.95 | 4.93 | 5.04 | 5.38 | 5.84 | 5.73 | 5.69 | 5.65 | 5.55 |
| 5 | 5.89 | 6.14 | 6.36 | 6.54 | 6.63 | 6.68 | 6.67 | 6.79 | 7.22 | 7.83 | 7.64 | 7.57 | 7.48 | 7.35 |
| 6 | 7.04 | 7.41 | 7.76 | 8.07 | 8.28 | 8.37 | 8.43 | 8.59 | 9.14 | 9.94 | 9.69 | 9.59 | 9.45 | 9.22 |
| 7 | 8.02 | 8.55 | 8.98 | 9.41 | 9.71 | 9.90 | 10.01 | 10.18 | 10.83 | 11.79 | 11.54 | 11.43 | 11.28 | 11.01 |
| 8 | 8.91 | 9.54 | 10.18 | 10.74 | 11.16 | 11.43 | 11.59 | 11.79 | 12.54 | 13.65 | 13.37 | 13.24 | 13.04 | 12.71 |
| 9 | ≈ 9.65 | 10.51 | 11.31 | 12.03 | 12.56 | 12.93 | 13.16 | 13.41 | 14.27 | 15.53 | 15.22 | 15.07 | 14.84 | 14.44 |
| 10 | ≈ 10.37 | 11.40 | 12.38 | 13.27 | 13.94 | 14.42 | 14.72 | 15.03 | 16.00 | 17.42 | 17.09 | 16.92 | 16.66 | 16.20 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.090 |
| SC2 | 0 | 8 | 11.791 |
| SC3 | -18 | 7 | 9.542 |
| SC4 | -25 | 6 | 7.760 |
| SC5 | -34 | 6 | 7.124 |
| A | 2407 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.