EA-150AC4-C10 C
10.62 kW
Defrost: None
Product code: EA-530AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,388 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 37.4 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 70 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 310 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC6-C01 C | None |
|---|---|
| EA-530AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.95 | 3.99 | 4.03 | 4.08 | 4.09 | 4.08 | 4.05 | 4.13 | 4.40 | 4.77 | 4.66 | 4.62 | 4.56 | 4.48 |
| 5 | 5.12 | 5.26 | 5.39 | 5.50 | 5.56 | 5.57 | 5.55 | 5.63 | 5.99 | 6.49 | 6.33 | 6.27 | 6.20 | 6.09 |
| 6 | 6.27 | 6.53 | 6.77 | 6.97 | 7.10 | 7.14 | 7.15 | 7.24 | 7.69 | 8.33 | 8.11 | 8.03 | 7.91 | 7.72 |
| 7 | 7.25 | 7.62 | 7.97 | 8.28 | 8.46 | 8.61 | 8.68 | 8.82 | 9.38 | 10.21 | 9.99 | 9.89 | 9.74 | 9.49 |
| 8 | 8.12 | 8.63 | 9.05 | 9.47 | 9.77 | 9.97 | 10.09 | 10.25 | 10.90 | 11.86 | 11.63 | 11.53 | 11.37 | 11.11 |
| 9 | 8.91 | 9.51 | 10.11 | 10.65 | 11.05 | 11.32 | 11.49 | 11.69 | 12.43 | 13.53 | 13.28 | 13.16 | 12.98 | 12.67 |
| 10 | 9.51 | 10.38 | 11.13 | 11.80 | 12.30 | 12.66 | 12.88 | 13.13 | 13.97 | 15.21 | 14.94 | 14.81 | 14.61 | 14.25 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.941 |
| SC2 | 0 | 8 | 10.248 |
| SC3 | -18 | 7 | 8.378 |
| SC4 | -25 | 6 | 6.765 |
| SC5 | -34 | 6 | 6.329 |
| A | 2407 mm |
|---|---|
| B | 523 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 428 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 523 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.