EA-240AE8-C01 C
10.47 kW
Defrost: None
Product code: EA-530AE8-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,116 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 43.4 m² |
| Inner volume | 16.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 69 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-530AE8-C05 C | None |
|---|---|
| EA-530AE8-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.99 | 4.03 | 4.08 | 4.13 | 4.15 | 4.14 | 4.11 | 4.23 | 4.52 | 4.91 | 4.82 | 4.79 | 4.76 | 4.70 |
| 5 | 5.12 | 5.25 | 5.38 | 5.49 | 5.54 | 5.55 | 5.51 | 5.63 | 5.99 | 6.50 | 6.33 | 6.27 | 6.18 | 6.06 |
| 6 | 6.24 | 6.43 | 6.66 | 6.85 | 6.97 | 7.01 | 6.98 | 7.09 | 7.53 | 8.17 | 7.93 | 7.83 | 7.69 | 7.46 |
| 7 | 7.25 | 7.61 | 7.94 | 8.22 | 8.41 | 8.48 | 8.48 | 8.60 | 9.13 | 9.90 | 9.61 | 9.49 | 9.30 | 8.99 |
| 8 | 8.17 | 8.65 | 9.09 | 9.49 | 9.76 | 9.92 | 9.95 | 10.11 | 10.73 | 11.63 | 11.31 | 11.17 | 10.94 | 10.56 |
| 9 | 8.98 | 9.60 | 10.17 | 10.62 | 10.97 | 11.19 | 11.30 | 11.50 | 12.21 | 13.26 | 12.95 | 12.80 | 12.57 | 12.18 |
| 10 | 9.72 | 10.48 | 11.12 | 11.74 | 12.20 | 12.49 | 12.64 | 12.87 | 13.68 | 14.85 | 14.52 | 14.35 | 14.09 | 13.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.519 |
| SC2 | 0 | 8 | 10.113 |
| SC3 | -18 | 7 | 8.309 |
| SC4 | -25 | 6 | 6.657 |
| SC5 | -34 | 6 | 6.295 |
| A | 2407 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.