EA-463GD7-C13 C
81.65 kW
Defrost: Electric
Product code: EA-563FD7-C08 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 76,886 m³/h |
|---|---|
| Air throw | 45 m |
| External surface | 352.1 m² |
| Inner volume | 106.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 594 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FD7-C08 C | None |
|---|---|
| EA-563FD7-C08 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 30.40 | 30.28 | 30.26 | 30.31 | 30.19 | 29.99 | 29.74 | 29.96 | 31.69 | 34.23 | 33.38 | 33.07 | 32.63 | 31.98 |
| 5 | 40.23 | 40.68 | 41.10 | 41.46 | 41.43 | 41.25 | 40.91 | 41.19 | 43.67 | 47.17 | 45.94 | 45.46 | 44.78 | 43.74 |
| 6 | 49.54 | 50.91 | 52.11 | 52.87 | 53.32 | 53.36 | 53.10 | 53.39 | 56.59 | 61.10 | 59.41 | 58.79 | 57.91 | 56.58 |
| 7 | 57.87 | 60.18 | 62.31 | 64.23 | 65.45 | 65.92 | 65.91 | 66.32 | 70.30 | 76.01 | 73.93 | 73.13 | 71.96 | 70.11 |
| 8 | 65.05 | 68.36 | 71.39 | 74.06 | 75.87 | 77.02 | 77.64 | 78.53 | 83.44 | 90.60 | 88.71 | 87.96 | 86.84 | 84.62 |
| 9 | 71.67 | 76.11 | 80.14 | 83.68 | 86.17 | 87.78 | 88.73 | 89.82 | 95.46 | 103.72 | 101.60 | 100.73 | 99.43 | 97.26 |
| 10 | 77.73 | 83.37 | 88.53 | 93.06 | 96.31 | 98.49 | 99.84 | 101.19 | 107.59 | 116.98 | 114.66 | 113.69 | 112.22 | 109.69 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 27.21 | 26.99 | 26.92 | 26.95 | 26.87 | 26.72 | 26.53 | 26.90 | 28.49 | 30.81 | 30.12 | 29.87 | 29.51 | 28.98 |
| 5 | 35.96 | 36.09 | 36.29 | 36.45 | 36.45 | 36.27 | 35.97 | 36.35 | 38.58 | 41.72 | 40.71 | 40.36 | 39.86 | 39.07 |
| 6 | 44.41 | 45.19 | 45.90 | 46.54 | 46.75 | 46.65 | 46.29 | 46.64 | 49.45 | 53.44 | 51.98 | 51.42 | 50.68 | 49.56 |
| 7 | 52.41 | 54.05 | 55.25 | 56.49 | 57.14 | 57.30 | 57.10 | 57.48 | 60.92 | 65.85 | 63.97 | 63.27 | 62.24 | 60.63 |
| 8 | 59.44 | 61.85 | 64.09 | 66.11 | 67.44 | 68.22 | 68.24 | 68.73 | 72.86 | 78.86 | 76.67 | 75.80 | 74.53 | 72.47 |
| 9 | 65.74 | 69.06 | 72.10 | 74.80 | 76.62 | 77.74 | 78.31 | 79.18 | 84.11 | 91.33 | 89.30 | 88.47 | 87.23 | 84.78 |
| 10 | 71.56 | 75.89 | 79.83 | 83.30 | 85.71 | 87.24 | 88.08 | 89.11 | 94.67 | 102.82 | 100.58 | 99.63 | 98.20 | 95.80 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 114.664 | 100.582 |
| SC2 | 0 | 8 | 78.527 | 68.732 |
| SC3 | -18 | 7 | 64.797 | 56.813 |
| SC4 | -25 | 6 | 52.109 | 45.904 |
| SC5 | -34 | 6 | 49.908 | 44.635 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| G | 985 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.