EA-563FE7-C08 C
94.92 kW
Defrost: None
Product code: EA-563FG10-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 56,484 m³/h |
|---|---|
| Air throw | 33 m |
| External surface | 406.9 m² |
| Inner volume | 166.7 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 631 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | D |
| Inlet | Ø54 |
|---|---|
| Outlet | Ø80 |
| EA-563FG10-C19 C | None |
|---|---|
| EA-563FG10-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 37.73 | 37.20 | 36.94 | 36.87 | 36.66 | 36.38 | 36.05 | 36.36 | 38.56 | 41.66 | 40.64 | 40.26 | 39.72 | 38.91 |
| 5 | 49.56 | 49.39 | 49.43 | 49.59 | 49.46 | 49.14 | 48.68 | 48.89 | 51.79 | 55.95 | 54.43 | 53.89 | 53.13 | 51.98 |
| 6 | 61.42 | 61.84 | 62.36 | 62.92 | 62.95 | 62.73 | 62.25 | 62.39 | 66.04 | 71.30 | 69.21 | 68.44 | 67.32 | 65.60 |
| 7 | 72.62 | 73.93 | 75.20 | 76.37 | 76.87 | 76.87 | 76.47 | 76.55 | 81.03 | 87.51 | 84.89 | 83.83 | 82.36 | 80.01 |
| 8 | 83.19 | 85.60 | 87.49 | 89.46 | 90.56 | 90.97 | 90.81 | 91.04 | 96.39 | 104.19 | 101.12 | 99.91 | 98.12 | 95.19 |
| 9 | 93.05 | 96.18 | 99.44 | 102.44 | 104.31 | 105.17 | 105.35 | 105.80 | 112.08 | 121.22 | 117.88 | 116.48 | 114.40 | 110.93 |
| 10 | 101.29 | 105.96 | 110.27 | 114.16 | 116.73 | 118.39 | 119.26 | 120.31 | 127.69 | 138.43 | 134.83 | 133.28 | 130.94 | 126.96 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 32.99 | 32.44 | 32.19 | 32.14 | 32.00 | 31.81 | 31.57 | 31.94 | 33.93 | 36.74 | 35.97 | 35.67 | 35.24 | 34.59 |
| 5 | 43.21 | 42.84 | 42.75 | 42.83 | 42.71 | 42.46 | 42.09 | 42.37 | 44.92 | 48.58 | 47.33 | 46.88 | 46.26 | 45.34 |
| 6 | 53.57 | 53.39 | 53.63 | 53.98 | 54.00 | 53.77 | 53.34 | 53.53 | 56.69 | 61.26 | 59.51 | 58.86 | 57.93 | 56.49 |
| 7 | 63.51 | 64.05 | 64.72 | 65.45 | 65.63 | 65.52 | 65.10 | 65.24 | 69.06 | 74.61 | 72.37 | 71.51 | 70.24 | 68.22 |
| 8 | 73.04 | 74.34 | 75.64 | 76.89 | 77.49 | 77.57 | 77.23 | 77.33 | 81.84 | 88.43 | 85.75 | 84.64 | 83.05 | 80.47 |
| 9 | 82.07 | 84.28 | 86.38 | 88.01 | 89.04 | 89.46 | 89.32 | 89.58 | 94.83 | 102.46 | 99.45 | 98.20 | 96.34 | 93.25 |
| 10 | 90.55 | 93.48 | 96.45 | 99.12 | 100.69 | 101.48 | 101.58 | 102.02 | 108.03 | 116.76 | 113.49 | 112.07 | 109.94 | 106.24 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 134.830 | 113.492 |
| SC2 | 0 | 8 | 91.038 | 77.331 |
| SC3 | -18 | 7 | 76.642 | 65.593 |
| SC4 | -25 | 6 | 62.362 | 53.631 |
| SC5 | -34 | 6 | 61.595 | 53.625 |
| A | 5415 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø54 |
| D OUT | 1 x Ø80 |
| Length | 5415 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.