Skip to Content

Unit cooler EA-663EE7-C01 C ED

Defrost: Electric

Unit cooler EA-663EE7-C01 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-663EE7-C01 C ED

Cooling capacity i
77.05 kW
Air flow
47,765 m³/h
Fin spacing
7.0 mm
Air throw
25 m
Fans
6 × ⌀630 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 6 — Number of fans (one digit).
  • C
    Fan diameter: 63 — Ø630 mm
  • D
    Dimensional data - coil size letter: E — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 7 — Fin spacing about 7 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole; Ø630: 230V/1Ph/50Hz, 6-pole; Ø800: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 47,765 m³/h
Air throw 25 m
External surface 405.6 m²
Inner volume 122.3 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 552 kg
Fans
Quantity 6
Diameter 630 mm
Speed 860 rpm
Power 3,600 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 59.0 dB(A)
Sound power 82.4 dB(A)
Energy class C
Connections
Inlet Ø54
Outlet Ø80
Defrost
EA-663EE7-C01 C None
EA-663EE7-C01 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
73.768 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 30.40 30.11 30.04 30.10 30.04 29.89 29.69 30.30 32.21 34.88 34.16 33.90 33.52 32.96
5 39.91 39.79 39.96 40.21 40.20 40.01 39.67 40.22 42.73 46.27 45.18 44.81 44.28 43.51
6 49.17 49.72 50.30 50.88 51.04 50.84 50.45 50.92 54.00 58.41 56.81 56.23 55.40 54.15
7 58.06 59.38 60.61 61.69 62.18 62.07 61.72 62.14 65.82 71.19 69.10 68.30 67.14 65.29
8 66.43 68.39 70.43 72.20 73.19 73.53 73.32 73.77 78.15 84.56 82.03 81.03 79.53 77.13
9 73.61 76.68 79.53 82.10 83.77 84.72 85.07 85.64 90.75 98.21 95.38 94.19 92.42 89.50
10 80.34 84.41 88.14 91.46 93.60 94.92 95.49 96.50 102.41 111.07 108.41 107.25 105.49 102.14

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 108.411
SC2 0 8 73.768
SC3 -18 7 61.953
SC4 -25 6 50.304
SC5 -34 6 49.356

Dimensions

Dimension drawing of EA-663EE7-C01 C
Dimension drawing
Dimensions as drawn
A 5215 mm
B 1000 mm
C 1190 mm
F 960 mm
E1 818 mm
E2 800 mm
E 4835 mm
D IN 1 x Ø54
D OUT 1 x Ø80
Overall [mm]
Length 5215 mm
Width 1000 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.