EA-HL-250AE10-A10 C
25.99 kW
Defrost: Electric
Product code: EA-HL-250AC4-A10 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,417 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 101.3 m² |
| Inner volume | 22.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 149 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 1,380 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.6 dB(A) |
| Energy class | D |
| Inlet | Ø35 |
|---|---|
| Outlet | Ø42 |
| EA-HL-250AC4-A10 C | None |
|---|---|
| EA-HL-250AC4-A10 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 9.69 | 9.61 | 9.57 | 9.57 | 9.53 | 9.46 | 9.39 | 9.49 | 10.04 | 10.86 | 10.62 | 10.53 | 10.41 | 10.23 |
| 5 | 12.93 | 13.01 | 13.09 | 13.18 | 13.17 | 13.09 | 12.98 | 13.04 | 13.82 | 14.93 | 14.55 | 14.41 | 14.22 | 13.95 |
| 6 | 16.20 | 16.52 | 16.82 | 17.07 | 17.13 | 17.11 | 17.00 | 17.05 | 18.05 | 19.49 | 18.93 | 18.73 | 18.44 | 18.01 |
| 7 | 19.02 | 19.61 | 20.18 | 20.70 | 21.04 | 21.23 | 21.27 | 21.35 | 22.60 | 24.43 | 23.73 | 23.46 | 23.07 | 22.47 |
| 8 | 21.53 | 22.44 | 23.16 | 23.90 | 24.40 | 24.70 | 24.86 | 25.09 | 26.64 | 28.92 | 28.28 | 28.03 | 27.65 | 27.05 |
| 9 | 23.87 | 24.99 | 26.12 | 27.12 | 27.81 | 28.25 | 28.49 | 28.78 | 30.56 | 33.18 | 32.46 | 32.17 | 31.72 | 30.99 |
| 10 | 25.91 | 27.51 | 28.98 | 30.28 | 31.18 | 31.78 | 32.14 | 32.51 | 34.53 | 37.50 | 36.72 | 36.38 | 35.88 | 35.03 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.62 | 8.52 | 8.48 | 8.49 | 8.47 | 8.43 | 8.38 | 8.51 | 9.04 | 9.79 | 9.60 | 9.53 | 9.43 | 9.28 |
| 5 | 11.46 | 11.45 | 11.48 | 11.54 | 11.53 | 11.47 | 11.38 | 11.48 | 12.18 | 13.19 | 12.87 | 12.77 | 12.62 | 12.41 |
| 6 | 14.35 | 14.51 | 14.63 | 14.80 | 14.85 | 14.81 | 14.71 | 14.79 | 15.67 | 16.94 | 16.47 | 16.30 | 16.06 | 15.71 |
| 7 | 17.09 | 17.49 | 17.87 | 18.20 | 18.36 | 18.36 | 18.27 | 18.35 | 19.43 | 21.00 | 20.38 | 20.15 | 19.81 | 19.28 |
| 8 | 19.45 | 20.08 | 20.68 | 21.24 | 21.60 | 21.76 | 21.85 | 22.05 | 23.36 | 25.26 | 24.54 | 24.25 | 23.82 | 23.14 |
| 9 | 21.65 | 22.55 | 23.29 | 24.04 | 24.55 | 24.85 | 25.00 | 25.23 | 26.79 | 29.06 | 28.40 | 28.13 | 27.71 | 27.03 |
| 10 | 23.69 | 24.79 | 25.89 | 26.87 | 27.52 | 27.95 | 28.17 | 28.46 | 30.21 | 32.78 | 32.05 | 31.73 | 31.25 | 30.46 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 36.719 | 32.047 |
| SC2 | 0 | 8 | 25.090 | 22.052 |
| SC3 | -18 | 7 | 20.855 | 18.282 |
| SC4 | -25 | 6 | 16.816 | 14.634 |
| SC5 | -34 | 6 | 16.291 | 14.405 |
| A | 2387 mm |
|---|---|
| B | 590 mm |
| C | 875 mm |
| F | 510 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 1 x Ø35 |
| D OUT | 1 x Ø42 |
| Length | 2387 mm |
|---|---|
| Width | 590 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.