Skip to Content

Unit cooler EA-HL-350AG10-A10 C ED

Defrost: Electric

Unit cooler EA-HL-350AG10-A10 C
Illustrative photo

Producer: Karyer · Line: EA-HL (High Type)

Product code: EA-HL-350AG10-A10 C ED

Cooling capacity i
46.44 kW
Air flow
22,161 m³/h
Fin spacing
10.0 mm
Air throw
23 m
Fans
3 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA-HL — EA-HL - high-type EA unit cooler (Ø500 fans)
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 50 — Ø500 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: G — 8 tube rows
  • F
    Fin spacing: 10 — Fin spacing about 10 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 10 — Ø500: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 22,161 m³/h
Air throw 23 m
External surface 139.1 m²
Inner volume 64.1 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 290 kg
Fans
Quantity 3
Diameter 500 mm
Speed 1,360 rpm
Power 2,070 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 62.0 dB(A)
Sound power 85.1 dB(A)
Energy class B
Connections
Inlet Ø35
Outlet Ø66,7
Defrost
EA-HL-350AG10-A10 C None
EA-HL-350AG10-A10 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
44.728 kW
Low speed (Y)
37.623 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 17.67 17.72 17.83 17.96 17.98 17.90 17.76 17.95 19.05 20.61 20.11 19.94 19.69 19.27
5 22.86 23.26 23.68 24.07 24.25 24.27 24.16 24.36 25.83 27.95 27.19 26.91 26.52 25.92
6 27.97 28.78 29.47 30.21 30.65 30.84 30.83 31.07 32.95 35.68 34.71 34.33 33.76 32.84
7 32.61 33.96 35.23 36.36 37.10 37.52 37.62 37.94 40.25 43.65 42.52 42.06 41.36 40.20
8 36.80 38.65 40.39 41.98 43.10 43.70 44.15 44.73 47.54 51.58 50.38 49.86 49.06 47.69
9 40.55 42.99 45.26 47.08 48.54 49.56 50.20 50.92 54.13 58.84 57.71 57.19 56.39 54.98
10 43.99 47.07 49.63 52.16 54.05 55.37 56.22 57.11 60.74 66.05 64.84 64.27 63.37 61.80

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 15.35 15.31 15.34 15.43 15.43 15.36 15.24 15.46 16.44 17.81 17.41 17.28 17.09 16.83
5 19.90 20.07 20.30 20.55 20.65 20.63 20.51 20.71 21.97 23.79 23.15 22.92 22.59 22.10
6 24.27 24.76 25.26 25.75 26.01 26.09 26.02 26.22 27.79 30.10 29.25 28.92 28.44 27.66
7 28.60 29.42 30.23 30.93 31.41 31.63 31.65 31.88 33.80 36.61 35.60 35.18 34.56 33.53
8 32.53 33.80 35.01 36.11 36.83 37.21 37.30 37.62 39.90 43.22 42.11 41.62 40.88 39.62
9 36.15 37.85 39.46 40.94 41.95 42.62 42.98 43.35 45.96 49.82 48.62 48.07 47.23 45.78
10 39.39 41.59 43.65 45.49 46.63 47.53 48.05 48.69 51.72 56.16 55.00 54.44 53.60 52.02

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 64.84055.002
SC2 0 8 44.72837.623
SC3 -18 7 36.70231.151
SC4 -25 6 29.46825.258
SC5 -34 6 28.17924.406

Dimensions

Dimension drawing of EA-HL-350AG10-A10 C
Dimension drawing
Dimensions as drawn
A 3387 mm
B 740 mm
C 875 mm
F 660 mm
E1 1018 mm
E2 1000 mm
E 3035 mm
D IN 1 x Ø35
D OUT 1 x Ø66,7
Overall [mm]
Length 3387 mm
Width 740 mm
Height 875 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.