EB-425BC4-B05 C
7.03 kW
Defrost: None
Product code: EB-145AE7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,605 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 18.1 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 46 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-145AE7-B01 C | None |
|---|---|
| EB-145AE7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.54 | 2.49 | 2.46 | 2.44 | 2.41 | 2.38 | 2.34 | 2.39 | 2.53 | 2.73 | 2.66 | 2.63 | 2.59 | 2.54 |
| 5 | 3.45 | 3.43 | 3.42 | 3.41 | 3.38 | 3.34 | 3.28 | 3.33 | 3.53 | 3.81 | 3.70 | 3.67 | 3.62 | 3.55 |
| 6 | 4.36 | 4.39 | 4.43 | 4.46 | 4.45 | 4.41 | 4.34 | 4.38 | 4.64 | 5.00 | 4.82 | 4.77 | 4.69 | 4.57 |
| 7 | 5.24 | 5.35 | 5.45 | 5.54 | 5.57 | 5.54 | 5.48 | 5.51 | 5.83 | 6.28 | 6.05 | 5.96 | 5.84 | 5.65 |
| 8 | 6.00 | 6.18 | 6.36 | 6.52 | 6.62 | 6.66 | 6.66 | 6.69 | 7.08 | 7.65 | 7.38 | 7.27 | 7.11 | 6.86 |
| 9 | 6.76 | 7.00 | 7.22 | 7.43 | 7.57 | 7.64 | 7.65 | 7.73 | 8.19 | 8.88 | 8.64 | 8.54 | 8.39 | 8.12 |
| 10 | 7.43 | 7.77 | 8.08 | 8.36 | 8.52 | 8.62 | 8.65 | 8.74 | 9.27 | 10.05 | 9.78 | 9.66 | 9.49 | 9.18 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.781 |
| SC2 | 0 | 8 | 6.692 |
| SC3 | -18 | 7 | 5.555 |
| SC4 | -25 | 6 | 4.429 |
| SC5 | -34 | 6 | 4.372 |
| A | 1017 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1017 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |