EB-130AE4-B01 C
2.76 kW
Defrost: None
Product code: EB-225AB4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,653 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 10.3 m² |
| Inner volume | 1.8 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 24 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.5 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EB-225AB4-B05 C | None |
|---|---|
| EB-225AB4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.05 | 1.04 | 1.05 | 1.05 | 1.06 | 1.06 | 1.05 | 1.07 | 1.14 | 1.23 | 1.21 | 1.20 | 1.19 | 1.17 |
| 5 | 1.37 | 1.39 | 1.40 | 1.42 | 1.43 | 1.43 | 1.43 | 1.44 | 1.53 | 1.66 | 1.62 | 1.61 | 1.59 | 1.56 |
| 6 | 1.69 | 1.73 | 1.77 | 1.81 | 1.83 | 1.83 | 1.83 | 1.85 | 1.96 | 2.12 | 2.07 | 2.05 | 2.02 | 1.98 |
| 7 | 1.98 | 2.04 | 2.11 | 2.17 | 2.21 | 2.24 | 2.25 | 2.28 | 2.42 | 2.62 | 2.56 | 2.53 | 2.49 | 2.43 |
| 8 | 2.26 | 2.35 | 2.42 | 2.50 | 2.56 | 2.60 | 2.62 | 2.65 | 2.82 | 3.06 | 3.00 | 2.98 | 2.94 | 2.88 |
| 9 | 2.51 | 2.63 | 2.74 | 2.85 | 2.92 | 2.96 | 2.99 | 3.03 | 3.22 | 3.50 | 3.43 | 3.40 | 3.36 | 3.28 |
| 10 | 2.74 | 2.90 | 3.04 | 3.18 | 3.27 | 3.33 | 3.37 | 3.41 | 3.63 | 3.94 | 3.87 | 3.83 | 3.78 | 3.69 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.866 |
| SC2 | 0 | 8 | 2.651 |
| SC3 | -18 | 7 | 2.186 |
| SC4 | -25 | 6 | 1.771 |
| SC5 | -34 | 6 | 1.704 |
| A | 1197 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1197 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.