EB-320AC4-C05 C
3.16 kW
Defrost: None
Product code: EB-225AC4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,551 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 13.8 m² |
| Inner volume | 2.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 26 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.5 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EB-225AC4-B05 C | None |
|---|---|
| EB-225AC4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.24 | 1.24 | 1.24 | 1.25 | 1.25 | 1.25 | 1.24 | 1.27 | 1.35 | 1.47 | 1.44 | 1.43 | 1.42 | 1.41 |
| 5 | 1.62 | 1.63 | 1.64 | 1.66 | 1.67 | 1.66 | 1.65 | 1.68 | 1.79 | 1.94 | 1.89 | 1.88 | 1.86 | 1.83 |
| 6 | 2.00 | 2.03 | 2.06 | 2.09 | 2.11 | 2.11 | 2.10 | 2.12 | 2.25 | 2.44 | 2.37 | 2.35 | 2.31 | 2.26 |
| 7 | 2.36 | 2.42 | 2.48 | 2.53 | 2.57 | 2.58 | 2.57 | 2.59 | 2.74 | 2.97 | 2.89 | 2.86 | 2.81 | 2.73 |
| 8 | 2.68 | 2.77 | 2.86 | 2.94 | 2.99 | 3.03 | 3.03 | 3.07 | 3.26 | 3.53 | 3.43 | 3.39 | 3.32 | 3.22 |
| 9 | 3.01 | 3.12 | 3.22 | 3.33 | 3.40 | 3.44 | 3.46 | 3.50 | 3.71 | 4.03 | 3.93 | 3.89 | 3.83 | 3.72 |
| 10 | 3.29 | 3.45 | 3.59 | 3.73 | 3.80 | 3.86 | 3.89 | 3.93 | 4.17 | 4.52 | 4.42 | 4.37 | 4.30 | 4.17 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.419 |
| SC2 | 0 | 8 | 3.069 |
| SC3 | -18 | 7 | 2.549 |
| SC4 | -25 | 6 | 2.061 |
| SC5 | -34 | 6 | 2.008 |
| A | 1197 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1197 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.