EB-325AC7-B05 C
4.15 kW
Defrost: None
Product code: EB-230BC6-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,480 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 14.2 m² |
| Inner volume | 3.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 32 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-230BC6-B05 C | None |
|---|---|
| EB-230BC6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.59 | 1.57 | 1.56 | 1.56 | 1.55 | 1.54 | 1.53 | 1.56 | 1.66 | 1.80 | 1.76 | 1.75 | 1.73 | 1.70 |
| 5 | 2.12 | 2.10 | 2.10 | 2.11 | 2.10 | 2.09 | 2.07 | 2.10 | 2.23 | 2.42 | 2.36 | 2.34 | 2.31 | 2.27 |
| 6 | 2.65 | 2.65 | 2.67 | 2.69 | 2.70 | 2.69 | 2.67 | 2.69 | 2.85 | 3.08 | 3.00 | 2.97 | 2.92 | 2.86 |
| 7 | 3.17 | 3.20 | 3.25 | 3.30 | 3.32 | 3.32 | 3.30 | 3.32 | 3.51 | 3.80 | 3.69 | 3.64 | 3.58 | 3.48 |
| 8 | 3.66 | 3.74 | 3.83 | 3.90 | 3.95 | 3.96 | 3.95 | 3.97 | 4.21 | 4.55 | 4.42 | 4.36 | 4.28 | 4.15 |
| 9 | 4.10 | 4.22 | 4.34 | 4.45 | 4.53 | 4.57 | 4.59 | 4.64 | 4.92 | 5.32 | 5.17 | 5.11 | 5.01 | 4.85 |
| 10 | 4.55 | 4.70 | 4.84 | 4.98 | 5.08 | 5.14 | 5.17 | 5.22 | 5.55 | 6.01 | 5.88 | 5.81 | 5.72 | 5.56 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.876 |
| SC2 | 0 | 8 | 3.971 |
| SC3 | -18 | 7 | 3.308 |
| SC4 | -25 | 6 | 2.671 |
| SC5 | -34 | 6 | 2.652 |
| A | 1357 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.