EB-430BE6-B01 C
11.77 kW
Defrost: None
Product code: EB-245AC6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,218 m³/h |
|---|---|
| Air throw | 17 m |
| External surface | 27.7 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 71 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | E |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-245AC6-B01 C | None |
|---|---|
| EB-245AC6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.38 | 4.31 | 4.27 | 4.24 | 4.19 | 4.13 | 4.07 | 4.11 | 4.34 | 4.67 | 4.54 | 4.49 | 4.42 | 4.32 |
| 5 | 5.95 | 5.98 | 6.00 | 6.02 | 5.99 | 5.92 | 5.83 | 5.88 | 6.24 | 6.72 | 6.52 | 6.45 | 6.35 | 6.19 |
| 6 | 7.46 | 7.60 | 7.76 | 7.90 | 7.94 | 7.90 | 7.82 | 7.87 | 8.34 | 8.99 | 8.69 | 8.59 | 8.45 | 8.24 |
| 7 | 8.72 | 8.98 | 9.23 | 9.46 | 9.61 | 9.68 | 9.69 | 9.81 | 10.42 | 11.30 | 11.03 | 10.93 | 10.77 | 10.46 |
| 8 | 9.99 | 10.37 | 10.72 | 11.05 | 11.23 | 11.35 | 11.39 | 11.52 | 12.24 | 13.28 | 12.96 | 12.84 | 12.65 | 12.35 |
| 9 | 11.13 | 11.66 | 12.15 | 12.59 | 12.88 | 13.06 | 13.12 | 13.27 | 14.09 | 15.30 | 14.94 | 14.79 | 14.56 | 14.18 |
| 10 | 12.19 | 12.89 | 13.54 | 14.12 | 14.51 | 14.75 | 14.84 | 15.02 | 15.96 | 17.33 | 16.93 | 16.75 | 16.49 | 16.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.926 |
| SC2 | 0 | 8 | 11.524 |
| SC3 | -18 | 7 | 9.530 |
| SC4 | -25 | 6 | 7.755 |
| SC5 | -34 | 6 | 7.497 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.