EB-225AC7-B05 C
2.63 kW
Defrost: None
Product code: EB-320AC7-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,307 m³/h |
|---|---|
| Air throw | 4 m |
| External surface | 11.4 m² |
| Inner volume | 3.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 27 kg |
| Quantity | 3 |
|---|---|
| Diameter | 200 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 60.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EB-320AC7-C05 C | None |
|---|---|
| EB-320AC7-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.04 | 1.04 | 1.04 | 1.05 | 1.05 | 1.05 | 1.05 | 1.07 | 1.13 | 1.23 | 1.21 | 1.20 | 1.19 | 1.17 |
| 5 | 1.35 | 1.35 | 1.36 | 1.38 | 1.39 | 1.40 | 1.40 | 1.41 | 1.49 | 1.62 | 1.59 | 1.57 | 1.56 | 1.53 |
| 6 | 1.65 | 1.67 | 1.69 | 1.72 | 1.74 | 1.75 | 1.76 | 1.77 | 1.88 | 2.04 | 1.99 | 1.97 | 1.95 | 1.91 |
| 7 | 1.94 | 1.98 | 2.02 | 2.07 | 2.10 | 2.12 | 2.13 | 2.14 | 2.27 | 2.47 | 2.41 | 2.39 | 2.36 | 2.30 |
| 8 | 2.22 | 2.28 | 2.35 | 2.41 | 2.46 | 2.49 | 2.50 | 2.52 | 2.68 | 2.91 | 2.85 | 2.82 | 2.78 | 2.72 |
| 9 | 2.48 | 2.57 | 2.66 | 2.74 | 2.81 | 2.85 | 2.88 | 2.91 | 3.09 | 3.36 | 3.29 | 3.26 | 3.21 | 3.14 |
| 10 | 2.72 | 2.84 | 2.95 | 3.06 | 3.14 | 3.19 | 3.23 | 3.28 | 3.49 | 3.79 | 3.73 | 3.70 | 3.65 | 3.57 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.726 |
| SC2 | 0 | 8 | 2.524 |
| SC3 | -18 | 7 | 2.081 |
| SC4 | -25 | 6 | 1.693 |
| SC5 | -34 | 6 | 1.654 |
| A | 1457 mm |
|---|---|
| B | 490 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 384 mm |
| E2 | 367 mm |
| E | 1135 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1457 mm |
|---|---|
| Width | 490 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.