EB-140AC7-B01 C
4.51 kW
Defrost: None
Product code: EB-325BC7-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,585 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 15.5 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 38 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-325BC7-B05 C | None |
|---|---|
| EB-325BC7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.71 | 1.72 | 1.73 | 1.75 | 1.76 | 1.76 | 1.76 | 1.78 | 1.89 | 2.05 | 2.01 | 2.00 | 1.98 | 1.95 |
| 5 | 2.20 | 2.25 | 2.29 | 2.34 | 2.36 | 2.38 | 2.38 | 2.40 | 2.55 | 2.76 | 2.70 | 2.68 | 2.64 | 2.59 |
| 6 | 2.68 | 2.76 | 2.85 | 2.93 | 2.98 | 3.01 | 3.02 | 3.05 | 3.24 | 3.51 | 3.43 | 3.40 | 3.36 | 3.28 |
| 7 | 3.12 | 3.25 | 3.37 | 3.49 | 3.58 | 3.64 | 3.68 | 3.72 | 3.95 | 4.29 | 4.20 | 4.16 | 4.10 | 4.01 |
| 8 | 3.51 | 3.69 | 3.86 | 4.02 | 4.13 | 4.21 | 4.27 | 4.33 | 4.60 | 5.01 | 4.92 | 4.88 | 4.83 | 4.73 |
| 9 | 3.91 | 4.13 | 4.35 | 4.54 | 4.68 | 4.78 | 4.85 | 4.93 | 5.25 | 5.71 | 5.61 | 5.57 | 5.50 | 5.39 |
| 10 | 4.25 | 4.54 | 4.80 | 5.04 | 5.23 | 5.36 | 5.44 | 5.53 | 5.89 | 6.41 | 6.31 | 6.26 | 6.19 | 6.05 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.311 |
| SC2 | 0 | 8 | 4.327 |
| SC3 | -18 | 7 | 3.530 |
| SC4 | -25 | 6 | 2.848 |
| SC5 | -34 | 6 | 2.700 |
| A | 1857 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1857 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.