EB-135AE4-B01 C
5.64 kW
Defrost: None
Product code: EB-330AC7-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,955 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 15.6 m² |
| Inner volume | 4.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 42 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.1 dB(A) |
| Energy class | C |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-330AC7-B01 C | None |
|---|---|
| EB-330AC7-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.10 | 2.09 | 2.10 | 2.11 | 2.10 | 2.09 | 2.07 | 2.11 | 2.24 | 2.42 | 2.36 | 2.34 | 2.31 | 2.26 |
| 5 | 2.77 | 2.80 | 2.85 | 2.88 | 2.90 | 2.89 | 2.87 | 2.91 | 3.09 | 3.34 | 3.25 | 3.22 | 3.18 | 3.12 |
| 6 | 3.41 | 3.51 | 3.60 | 3.68 | 3.73 | 3.74 | 3.73 | 3.77 | 4.00 | 4.33 | 4.20 | 4.16 | 4.09 | 3.99 |
| 7 | 3.98 | 4.13 | 4.27 | 4.41 | 4.50 | 4.56 | 4.59 | 4.65 | 4.94 | 5.37 | 5.23 | 5.17 | 5.08 | 4.95 |
| 8 | 4.53 | 4.74 | 4.91 | 5.10 | 5.22 | 5.31 | 5.35 | 5.42 | 5.76 | 6.27 | 6.13 | 6.08 | 5.99 | 5.85 |
| 9 | 5.02 | 5.29 | 5.55 | 5.79 | 5.95 | 6.06 | 6.12 | 6.20 | 6.60 | 7.17 | 7.02 | 6.96 | 6.86 | 6.70 |
| 10 | 5.47 | 5.83 | 6.16 | 6.45 | 6.66 | 6.81 | 6.89 | 6.99 | 7.43 | 8.08 | 7.91 | 7.84 | 7.73 | 7.54 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.913 |
| SC2 | 0 | 8 | 5.423 |
| SC3 | -18 | 7 | 4.451 |
| SC4 | -25 | 6 | 3.597 |
| SC5 | -34 | 6 | 3.433 |
| A | 1617 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1617 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |