EB-235AC7-B01 C
7.29 kW
Defrost: None
Product code: EB-330AE6-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,972 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 26.9 m² |
| Inner volume | 6.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-330AE6-B05 C | None |
|---|---|
| EB-330AE6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.90 | 2.91 | 2.93 | 2.95 | 2.96 | 2.95 | 2.92 | 3.01 | 3.21 | 3.50 | 3.43 | 3.41 | 3.38 | 3.35 |
| 5 | 3.74 | 3.78 | 3.84 | 3.89 | 3.91 | 3.91 | 3.87 | 3.95 | 4.19 | 4.55 | 4.43 | 4.38 | 4.32 | 4.22 |
| 6 | 4.54 | 4.64 | 4.75 | 4.85 | 4.89 | 4.90 | 4.87 | 4.93 | 5.23 | 5.67 | 5.49 | 5.42 | 5.31 | 5.14 |
| 7 | 5.31 | 5.48 | 5.65 | 5.80 | 5.88 | 5.91 | 5.88 | 5.94 | 6.30 | 6.82 | 6.60 | 6.51 | 6.38 | 6.16 |
| 8 | 6.00 | 6.24 | 6.47 | 6.68 | 6.81 | 6.87 | 6.88 | 6.97 | 7.39 | 7.99 | 7.75 | 7.63 | 7.48 | 7.20 |
| 9 | 6.69 | 6.96 | 7.26 | 7.53 | 7.70 | 7.80 | 7.82 | 7.91 | 8.39 | 9.08 | 8.84 | 8.72 | 8.56 | 8.26 |
| 10 | 7.30 | 7.70 | 8.07 | 8.40 | 8.59 | 8.72 | 8.76 | 8.86 | 9.40 | 10.17 | 9.90 | 9.77 | 9.58 | 9.25 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.898 |
| SC2 | 0 | 8 | 6.965 |
| SC3 | -18 | 7 | 5.837 |
| SC4 | -25 | 6 | 4.749 |
| SC5 | -34 | 6 | 4.569 |
| A | 1617 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1617 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.