EB-330AC4-B05 C
6.33 kW
Defrost: None
Product code: EB-330BC6-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,719 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 21.3 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EB-330BC6-B05 C | None |
|---|---|
| EB-330BC6-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.41 | 2.38 | 2.38 | 2.38 | 2.38 | 2.37 | 2.35 | 2.39 | 2.54 | 2.76 | 2.70 | 2.68 | 2.65 | 2.61 |
| 5 | 3.18 | 3.18 | 3.20 | 3.22 | 3.23 | 3.21 | 3.19 | 3.23 | 3.43 | 3.72 | 3.62 | 3.59 | 3.55 | 3.49 |
| 6 | 3.95 | 4.00 | 4.05 | 4.11 | 4.13 | 4.13 | 4.10 | 4.14 | 4.39 | 4.75 | 4.62 | 4.57 | 4.50 | 4.39 |
| 7 | 4.69 | 4.79 | 4.90 | 5.00 | 5.05 | 5.07 | 5.06 | 5.10 | 5.40 | 5.85 | 5.68 | 5.62 | 5.52 | 5.36 |
| 8 | 5.35 | 5.51 | 5.67 | 5.82 | 5.93 | 5.99 | 6.02 | 6.08 | 6.45 | 6.99 | 6.79 | 6.71 | 6.59 | 6.40 |
| 9 | 6.00 | 6.22 | 6.41 | 6.61 | 6.75 | 6.83 | 6.88 | 6.96 | 7.39 | 8.02 | 7.84 | 7.76 | 7.64 | 7.43 |
| 10 | 6.59 | 6.88 | 7.15 | 7.40 | 7.56 | 7.68 | 7.74 | 7.83 | 8.32 | 9.03 | 8.83 | 8.74 | 8.60 | 8.36 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.829 |
| SC2 | 0 | 8 | 6.083 |
| SC3 | -18 | 7 | 5.026 |
| SC4 | -25 | 6 | 4.049 |
| SC5 | -34 | 6 | 3.965 |
| A | 1857 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.