EB-445AC6-B01 C
22.50 kW
Defrost: None
Product code: EB-345AE6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 13,465 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 62.4 m² |
| Inner volume | 15.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 113 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,470 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EB-345AE6-B01 C | None |
|---|---|
| EB-345AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.40 | 8.62 | 8.82 | 8.98 | 9.03 | 9.01 | 8.92 | 9.19 | 9.80 | 10.62 | 10.38 | 10.28 | 10.14 | 9.93 |
| 5 | 10.80 | 11.27 | 11.70 | 12.08 | 12.33 | 12.41 | 12.36 | 12.62 | 13.43 | 14.57 | 14.18 | 14.04 | 13.85 | 13.59 |
| 6 | 12.80 | 13.52 | 14.17 | 14.76 | 15.14 | 15.37 | 15.45 | 15.77 | 16.78 | 18.26 | 17.86 | 17.71 | 17.48 | 17.11 |
| 7 | 14.77 | 15.75 | 16.65 | 17.44 | 17.99 | 18.29 | 18.45 | 18.80 | 20.00 | 21.76 | 21.26 | 21.06 | 20.75 | 20.24 |
| 8 | 16.46 | 17.76 | 18.95 | 20.01 | 20.77 | 21.25 | 21.49 | 21.81 | 23.18 | 25.24 | 24.68 | 24.44 | 24.07 | 23.38 |
| 9 | ≈ 17.99 | 19.62 | 21.14 | 22.50 | 23.32 | 23.98 | 24.37 | 24.86 | 26.46 | 28.79 | 28.20 | 27.91 | 27.44 | 26.59 |
| 10 | ≈ 19.36 | 21.33 | 23.20 | 24.66 | 25.89 | 26.77 | 27.30 | 27.91 | 29.71 | 32.35 | 31.73 | 31.41 | 30.86 | 29.87 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 31.725 |
| SC2 | 0 | 8 | 21.812 |
| SC3 | -18 | 7 | 17.691 |
| SC4 | -25 | 6 | 14.174 |
| SC5 | -34 | 6 | 12.966 |
| A | 2317 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 1985 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2317 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.