EB-330AC6-B01 C
5.97 kW
Defrost: None
Product code: EB-425BC7-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,446 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 20.4 m² |
| Inner volume | 5.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 48 kg |
| Quantity | 4 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.5 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EB-425BC7-B05 C | None |
|---|---|
| EB-425BC7-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.28 | 2.30 | 2.33 | 2.36 | 2.38 | 2.38 | 2.37 | 2.40 | 2.55 | 2.77 | 2.71 | 2.68 | 2.65 | 2.61 |
| 5 | 2.93 | 3.01 | 3.08 | 3.15 | 3.20 | 3.22 | 3.22 | 3.25 | 3.45 | 3.74 | 3.65 | 3.62 | 3.57 | 3.50 |
| 6 | 3.55 | 3.69 | 3.82 | 3.95 | 4.03 | 4.08 | 4.10 | 4.14 | 4.40 | 4.78 | 4.67 | 4.62 | 4.56 | 4.46 |
| 7 | 4.09 | 4.29 | 4.48 | 4.65 | 4.78 | 4.86 | 4.92 | 4.99 | 5.31 | 5.78 | 5.67 | 5.63 | 5.56 | 5.45 |
| 8 | 4.63 | 4.89 | 5.13 | 5.34 | 5.51 | 5.63 | 5.71 | 5.79 | 6.16 | 6.71 | 6.59 | 6.54 | 6.46 | 6.33 |
| 9 | 5.10 | 5.44 | 5.75 | 6.04 | 6.25 | 6.40 | 6.49 | 6.60 | 7.02 | 7.65 | 7.52 | 7.46 | 7.36 | 7.21 |
| 10 | 5.53 | 5.95 | 6.34 | 6.69 | 6.96 | 7.15 | 7.29 | 7.40 | 7.87 | 8.57 | 8.44 | 8.38 | 8.28 | 8.11 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.441 |
| SC2 | 0 | 8 | 5.793 |
| SC3 | -18 | 7 | 4.706 |
| SC4 | -25 | 6 | 3.823 |
| SC5 | -34 | 6 | 3.586 |
| A | 2357 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 2357 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.