EB-330AE4-B05 C
7.35 kW
Defrost: None
Product code: EB-430BB6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,858 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 21.3 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 70.7 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-430BB6-B01 C | None |
|---|---|
| EB-430BB6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.72 | 2.67 | 2.65 | 2.64 | 2.62 | 2.60 | 2.58 | 2.61 | 2.76 | 2.99 | 2.92 | 2.89 | 2.86 | 2.81 |
| 5 | 3.67 | 3.64 | 3.64 | 3.64 | 3.63 | 3.61 | 3.58 | 3.60 | 3.81 | 4.12 | 4.02 | 3.98 | 3.93 | 3.86 |
| 6 | 4.61 | 4.63 | 4.67 | 4.72 | 4.73 | 4.72 | 4.69 | 4.70 | 4.98 | 5.38 | 5.23 | 5.18 | 5.10 | 4.98 |
| 7 | 5.52 | 5.61 | 5.72 | 5.82 | 5.87 | 5.88 | 5.86 | 5.89 | 6.24 | 6.74 | 6.56 | 6.48 | 6.38 | 6.22 |
| 8 | 6.31 | 6.46 | 6.62 | 6.79 | 6.90 | 6.97 | 7.01 | 7.08 | 7.52 | 8.17 | 7.96 | 7.88 | 7.75 | 7.55 |
| 9 | 7.10 | 7.32 | 7.54 | 7.73 | 7.89 | 7.99 | 8.04 | 8.13 | 8.63 | 9.37 | 9.18 | 9.10 | 8.98 | 8.79 |
| 10 | 7.83 | 8.13 | 8.42 | 8.69 | 8.89 | 9.01 | 9.09 | 9.19 | 9.76 | 10.60 | 10.39 | 10.30 | 10.16 | 9.94 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.391 |
| SC2 | 0 | 8 | 7.078 |
| SC3 | -18 | 7 | 5.844 |
| SC4 | -25 | 6 | 4.673 |
| SC5 | -34 | 6 | 4.622 |
| A | 2357 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2035 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2357 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.