ED-A-C-130BC6-B25 C
1.03 kW
Defrost: None
Product code: ED-A-C-125AB6-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 505 m³/h |
|---|---|
| Air throw | 3 m |
| External surface | 3.0 m² |
| Inner volume | 0.3 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 9 kg |
| Quantity | 1 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 65 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 34.0 dB(A) |
|---|---|
| Sound power | 54.7 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø3/8" |
| ED-A-C-125AB6-B24 C | None |
|---|---|
| ED-A-C-125AB6-B24 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.26 | 0.25 | 0.24 | 0.24 | 0.24 | 0.24 | 0.23 | 0.24 | 0.25 | 0.28 | 0.27 | 0.27 | 0.27 | 0.26 |
| 5 | 0.35 | 0.34 | 0.33 | 0.33 | 0.33 | 0.32 | 0.32 | 0.32 | 0.34 | 0.37 | 0.36 | 0.36 | 0.35 | 0.35 |
| 6 | 0.45 | 0.44 | 0.44 | 0.43 | 0.43 | 0.42 | 0.41 | 0.41 | 0.44 | 0.47 | 0.46 | 0.45 | 0.44 | 0.43 |
| 7 | 0.54 | 0.54 | 0.54 | 0.54 | 0.54 | 0.53 | 0.52 | 0.52 | 0.55 | 0.59 | 0.56 | 0.56 | 0.54 | 0.53 |
| 8 | 0.63 | 0.64 | 0.65 | 0.66 | 0.65 | 0.65 | 0.63 | 0.63 | 0.66 | 0.71 | 0.68 | 0.67 | 0.66 | 0.63 |
| 9 | 0.71 | 0.73 | 0.74 | 0.75 | 0.76 | 0.76 | 0.75 | 0.75 | 0.79 | 0.85 | 0.81 | 0.80 | 0.78 | 0.75 |
| 10 | 0.79 | 0.82 | 0.83 | 0.85 | 0.86 | 0.86 | 0.85 | 0.85 | 0.90 | 0.97 | 0.94 | 0.93 | 0.91 | 0.87 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 0.942 |
| SC2 | 0 | 8 | 0.630 |
| SC3 | -18 | 7 | 0.541 |
| SC4 | -25 | 6 | 0.436 |
| SC5 | -34 | 6 | 0.444 |
| A | 645 mm |
|---|---|
| B | 455 mm |
| C | 150 mm |
| E | 330 mm |
| D | 595 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø3/8" |
| Length | 645 mm |
|---|---|
| Width | 455 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.