Skip to Content

Unit cooler ED-A-C-130AD6-B25 C

Unit cooler ED-A-C-130AD6-B25 C
Illustrative photo

Producer: Karyer · Line: ED-A C (Commercial Double Flow)

Product code: ED-A-C-130AD6-B25 C

Cooling capacity i
1.35 kW
Air flow
840 m³/h
Fin spacing
6.0 mm
Air throw
4 m
Fans
1 × ⌀300 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): ED-A — ED-A - commercial double-flow ceiling evaporator, aluminium casing
  • B
    Design type: C — Design type C
  • C
    Number of fans: 1 — Number of fans (one digit).
  • D
    Fan diameter: 30 — Ø300 mm
  • G
    Fin spacing: 6 — Fin spacing about 6 mm
  • H
    Generation code: B — Generation B
  • I
    Fan data: 25 — Ø300: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 840 m³/h
Air throw 4 m
External surface 5.6 m²
Inner volume 0.9 dm³
Fin spacing 6.0 mm
Fin materialAluminium
Net weight 11 kg
Fans
Quantity 1
Diameter 300 mm
Speed 1,300 rpm
Power 120 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 41.0 dB(A)
Sound power 62.0 dB(A)
Energy class E
Connections
Inlet Ø3/8"
Outlet Ø3/8"
Defrost
ED-A-C-130AD6-B25 C None
ED-A-C-130AD6-B25 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
1.305 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 0.45 0.49 0.52 0.55 0.57 0.58 0.58 0.61 0.65 0.71 0.70 0.69 0.69 0.68
5 0.55 0.61 0.66 0.71 0.74 0.76 0.77 0.80 0.85 0.93 0.91 0.91 0.90 0.88
6 ≈ 0.60 ≈ 0.71 0.78 0.84 0.89 0.92 0.94 0.97 1.03 1.13 1.11 1.10 1.09 1.06
7 not rated 0.81 0.90 0.98 1.04 1.09 1.11 1.14 1.21 1.32 1.30 1.29 1.27 1.24
8 ≈ 0.26 ≈ 0.89 1.00 1.10 1.18 1.23 1.27 1.31 1.39 1.52 1.50 1.49 1.46 1.43
9 ≈ 0.29 ≈ 0.59 ≈ 1.09 1.21 1.29 1.37 1.42 1.47 1.57 1.72 1.70 1.68 1.66 1.62
10 0.32 ≈ 0.32 ≈ 1.17 1.27 1.41 1.51 1.57 1.64 1.75 1.92 1.90 1.88 1.86 1.81

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 1.896
SC2 0 8 1.305
SC3 -18 7 1.004
SC4 -25 6 0.777
SC5 -34 6 0.648

Dimensions

Dimension drawing of ED-A-C-130AD6-B25 C
Dimension drawing
Dimensions as drawn
A 845 mm
B 475 mm
C 150 mm
E 350 mm
D 795 mm
D IN 1 x Ø3/8"
D OUT 1 x Ø3/8"
Overall [mm]
Length 845 mm
Width 475 mm
Height 150 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.