ED-A-C-130AC6-B25 C
1.11 kW
Defrost: Electric
Product code: ED-A-C-225AD6-B24 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 772 m³/h |
|---|---|
| Air throw | 3 m |
| External surface | 5.6 m² |
| Inner volume | 0.8 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 11 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 130 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 36.0 dB(A) |
|---|---|
| Sound power | 57.7 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø3/8" |
| ED-A-C-225AD6-B24 C | None |
|---|---|
| ED-A-C-225AD6-B24 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.43 | 0.45 | 0.48 | 0.50 | 0.51 | 0.51 | 0.51 | 0.53 | 0.56 | 0.61 | 0.60 | 0.60 | 0.59 | 0.58 |
| 5 | 0.53 | 0.57 | 0.62 | 0.65 | 0.67 | 0.69 | 0.69 | 0.71 | 0.75 | 0.82 | 0.80 | 0.79 | 0.78 | 0.76 |
| 6 | 0.62 | 0.68 | 0.73 | 0.78 | 0.82 | 0.84 | 0.85 | 0.87 | 0.93 | 1.01 | 0.99 | 0.98 | 0.97 | 0.95 |
| 7 | 0.69 | 0.77 | 0.85 | 0.92 | 0.96 | 0.99 | 1.01 | 1.03 | 1.10 | 1.20 | 1.17 | 1.16 | 1.14 | 1.11 |
| 8 | ≈ 0.75 | ≈ 0.87 | 0.96 | 1.04 | 1.10 | 1.14 | 1.17 | 1.19 | 1.26 | 1.38 | 1.35 | 1.33 | 1.31 | 1.28 |
| 9 | ≈ 0.35 | ≈ 0.94 | 1.05 | 1.15 | 1.23 | 1.27 | 1.31 | 1.34 | 1.43 | 1.56 | 1.53 | 1.52 | 1.49 | 1.45 |
| 10 | ≈ 0.29 | ≈ 0.94 | ≈ 1.14 | 1.26 | 1.34 | 1.41 | 1.45 | 1.50 | 1.60 | 1.75 | 1.72 | 1.70 | 1.67 | 1.62 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 1.716 |
| SC2 | 0 | 8 | 1.186 |
| SC3 | -18 | 7 | 0.936 |
| SC4 | -25 | 6 | 0.734 |
| SC5 | -34 | 6 | 0.631 |
| A | 1245 mm |
|---|---|
| B | 475 mm |
| C | 150 mm |
| E | 350 mm |
| D | 1195 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø3/8" |
| Length | 1245 mm |
|---|---|
| Width | 475 mm |
| Height | 150 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.