ED-DP-135AE4-B22 C
4.08 kW
Defrost: None
Product code: ED-DP-140AC7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,504 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 15.3 m² |
| Inner volume | 5.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 59 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.3 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-140AC7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.55 | 1.51 | 1.49 | 1.48 | 1.48 | 1.47 | 1.46 | 1.49 | 1.58 | 1.71 | 1.68 | 1.67 | 1.65 | 1.63 |
| 5 | 2.08 | 2.04 | 2.02 | 2.01 | 2.00 | 1.98 | 1.96 | 1.99 | 2.11 | 2.28 | 2.23 | 2.22 | 2.19 | 2.16 |
| 6 | 2.64 | 2.60 | 2.58 | 2.58 | 2.57 | 2.55 | 2.52 | 2.54 | 2.69 | 2.91 | 2.83 | 2.80 | 2.76 | 2.71 |
| 7 | 3.20 | 3.18 | 3.18 | 3.19 | 3.18 | 3.16 | 3.13 | 3.14 | 3.32 | 3.58 | 3.48 | 3.44 | 3.38 | 3.30 |
| 8 | 3.76 | 3.76 | 3.78 | 3.81 | 3.82 | 3.80 | 3.77 | 3.77 | 3.99 | 4.31 | 4.17 | 4.12 | 4.04 | 3.92 |
| 9 | 4.32 | 4.35 | 4.39 | 4.45 | 4.47 | 4.46 | 4.43 | 4.43 | 4.69 | 5.06 | 4.90 | 4.83 | 4.74 | 4.58 |
| 10 | 4.84 | 4.92 | 5.01 | 5.09 | 5.12 | 5.13 | 5.11 | 5.12 | 5.41 | 5.84 | 5.66 | 5.58 | 5.47 | 5.28 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.662 |
| SC2 | 0 | 8 | 3.770 |
| SC3 | -18 | 7 | 3.185 |
| SC4 | -25 | 6 | 2.584 |
| SC5 | -34 | 6 | 2.632 |
| A | 948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.