ED-DP-140AC4-B22 C
5.18 kW
Defrost: None
Product code: ED-DP-140AE7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,227 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 22.9 m² |
| Inner volume | 8.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 64 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.6 dB(A) |
| Energy class | A |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-140AE7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.94 | 1.92 | 1.92 | 1.92 | 1.92 | 1.91 | 1.90 | 1.95 | 2.08 | 2.26 | 2.22 | 2.21 | 2.19 | 2.16 |
| 5 | 2.53 | 2.53 | 2.54 | 2.56 | 2.56 | 2.55 | 2.53 | 2.57 | 2.73 | 2.96 | 2.89 | 2.86 | 2.83 | 2.78 |
| 6 | 3.11 | 3.14 | 3.18 | 3.22 | 3.23 | 3.23 | 3.20 | 3.23 | 3.43 | 3.71 | 3.61 | 3.57 | 3.51 | 3.42 |
| 7 | 3.68 | 3.75 | 3.82 | 3.89 | 3.93 | 3.93 | 3.90 | 3.93 | 4.17 | 4.51 | 4.36 | 4.31 | 4.23 | 4.09 |
| 8 | 4.25 | 4.36 | 4.46 | 4.57 | 4.63 | 4.64 | 4.62 | 4.65 | 4.93 | 5.32 | 5.16 | 5.09 | 4.98 | 4.80 |
| 9 | 4.76 | 4.94 | 5.10 | 5.25 | 5.33 | 5.36 | 5.35 | 5.39 | 5.70 | 6.16 | 5.98 | 5.89 | 5.76 | 5.55 |
| 10 | 5.24 | 5.48 | 5.71 | 5.91 | 6.02 | 6.08 | 6.09 | 6.13 | 6.49 | 7.02 | 6.81 | 6.71 | 6.57 | 6.32 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.809 |
| SC2 | 0 | 8 | 4.651 |
| SC3 | -18 | 7 | 3.910 |
| SC4 | -25 | 6 | 3.180 |
| SC5 | -34 | 6 | 3.122 |
| A | 948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.