ED-DP-145AC7-B24 C
5.81 kW
Defrost: None
Product code: ED-DP-140AE4-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,035 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 36.5 m² |
| Inner volume | 8.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 66 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 120 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-DP-140AE4-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.41 | 2.42 | 2.45 | 2.48 | 2.49 | 2.49 | 2.48 | 2.55 | 2.72 | 2.96 | 2.91 | 2.89 | 2.87 | 2.84 |
| 5 | 3.05 | 3.10 | 3.15 | 3.20 | 3.23 | 3.23 | 3.21 | 3.27 | 3.48 | 3.78 | 3.68 | 3.64 | 3.59 | 3.51 |
| 6 | 3.67 | 3.76 | 3.85 | 3.94 | 3.99 | 4.00 | 3.97 | 4.02 | 4.27 | 4.63 | 4.49 | 4.43 | 4.34 | 4.20 |
| 7 | 4.28 | 4.43 | 4.55 | 4.67 | 4.75 | 4.77 | 4.75 | 4.80 | 5.08 | 5.50 | 5.32 | 5.24 | 5.13 | 4.93 |
| 8 | 4.84 | 5.05 | 5.24 | 5.41 | 5.52 | 5.55 | 5.54 | 5.59 | 5.91 | 6.39 | 6.18 | 6.09 | 5.94 | 5.70 |
| 9 | 5.35 | 5.63 | 5.89 | 6.12 | 6.26 | 6.33 | 6.33 | 6.38 | 6.75 | 7.29 | 7.05 | 6.94 | 6.77 | 6.48 |
| 10 | 5.81 | 6.17 | 6.49 | 6.78 | 6.97 | 7.04 | 7.08 | 7.15 | 7.57 | 8.18 | 7.93 | 7.81 | 7.61 | 7.27 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.931 |
| SC2 | 0 | 8 | 5.585 |
| SC3 | -18 | 7 | 4.709 |
| SC4 | -25 | 6 | 3.854 |
| SC5 | -34 | 6 | 3.692 |
| A | 948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 635 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.