ED-DP-240AC4-B22 C
10.50 kW
Defrost: None
Product code: ED-DP-240AE7-B22 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,451 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 45.8 m² |
| Inner volume | 15.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 102 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 870 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.6 dB(A) |
| Energy class | A |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-240AE7-B22 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.02 | 4.07 | 4.13 | 4.19 | 4.21 | 4.21 | 4.19 | 4.29 | 4.58 | 4.97 | 4.88 | 4.85 | 4.81 | 4.75 |
| 5 | 5.12 | 5.25 | 5.39 | 5.51 | 5.57 | 5.59 | 5.56 | 5.66 | 6.02 | 6.53 | 6.36 | 6.30 | 6.21 | 6.08 |
| 6 | 6.20 | 6.40 | 6.63 | 6.83 | 6.95 | 7.00 | 6.99 | 7.09 | 7.52 | 8.16 | 7.93 | 7.84 | 7.70 | 7.47 |
| 7 | 7.18 | 7.54 | 7.87 | 8.16 | 8.35 | 8.43 | 8.45 | 8.55 | 9.07 | 9.84 | 9.56 | 9.45 | 9.27 | 8.96 |
| 8 | 8.08 | 8.56 | 9.01 | 9.40 | 9.68 | 9.84 | 9.88 | 10.02 | 10.62 | 11.52 | 11.21 | 11.07 | 10.86 | 10.49 |
| 9 | 8.87 | 9.48 | 10.06 | 10.50 | 10.86 | 11.09 | 11.20 | 11.38 | 12.09 | 13.12 | 12.82 | 12.68 | 12.45 | 12.04 |
| 10 | 9.59 | 10.35 | 10.99 | 11.60 | 12.06 | 12.36 | 12.52 | 12.73 | 13.53 | 14.68 | 14.36 | 14.20 | 13.94 | 13.49 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.359 |
| SC2 | 0 | 8 | 10.018 |
| SC3 | -18 | 7 | 8.250 |
| SC4 | -25 | 6 | 6.631 |
| SC5 | -34 | 6 | 6.262 |
| A | 1548 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1235 mm |
| E2 | 618 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1548 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.