ED-DP-340AC4-B22 C
15.47 kW
Defrost: None
Product code: ED-DP-245AC4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,154 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 64.9 m² |
| Inner volume | 14.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 120 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-245AC4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.89 | 5.88 | 5.91 | 5.94 | 5.95 | 5.93 | 5.90 | 6.02 | 6.41 | 6.96 | 6.83 | 6.79 | 6.73 | 6.62 |
| 5 | 7.67 | 7.76 | 7.86 | 7.96 | 8.00 | 7.98 | 7.93 | 8.05 | 8.55 | 9.27 | 9.04 | 8.97 | 8.86 | 8.71 |
| 6 | 9.45 | 9.68 | 9.89 | 10.08 | 10.16 | 10.17 | 10.12 | 10.22 | 10.84 | 11.74 | 11.41 | 11.29 | 11.11 | 10.83 |
| 7 | 11.07 | 11.45 | 11.81 | 12.15 | 12.36 | 12.45 | 12.42 | 12.52 | 13.27 | 14.35 | 13.94 | 13.77 | 13.53 | 13.14 |
| 8 | 12.48 | 13.03 | 13.54 | 13.95 | 14.25 | 14.43 | 14.50 | 14.67 | 15.57 | 16.91 | 16.50 | 16.33 | 16.06 | 15.56 |
| 9 | 13.79 | 14.54 | 15.14 | 15.75 | 16.15 | 16.40 | 16.52 | 16.72 | 17.75 | 19.26 | 18.80 | 18.60 | 18.30 | 17.77 |
| 10 | 15.01 | 15.88 | 16.75 | 17.51 | 18.04 | 18.37 | 18.54 | 18.78 | 19.94 | 21.63 | 21.14 | 20.91 | 20.55 | 19.95 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 21.137 |
| SC2 | 0 | 8 | 14.668 |
| SC3 | -18 | 7 | 12.245 |
| SC4 | -25 | 6 | 9.889 |
| SC5 | -34 | 6 | 9.512 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.