ED-DP-240AE4-B22 C
11.61 kW
Defrost: None
Product code: ED-DP-245AC7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,616 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 40.4 m² |
| Inner volume | 13.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 109 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.2 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| ED-DP-245AC7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.15 | 4.15 | 4.16 | 4.17 | 4.16 | 4.13 | 4.10 | 4.15 | 4.40 | 4.75 | 4.63 | 4.59 | 4.52 | 4.43 |
| 5 | 5.47 | 5.55 | 5.64 | 5.71 | 5.74 | 5.72 | 5.68 | 5.73 | 6.08 | 6.57 | 6.40 | 6.34 | 6.25 | 6.13 |
| 6 | 6.78 | 6.98 | 7.16 | 7.30 | 7.39 | 7.42 | 7.40 | 7.46 | 7.91 | 8.55 | 8.31 | 8.22 | 8.09 | 7.89 |
| 7 | 7.97 | 8.31 | 8.62 | 8.90 | 9.09 | 9.18 | 9.19 | 9.27 | 9.83 | 10.65 | 10.35 | 10.24 | 10.07 | 9.81 |
| 8 | 8.98 | 9.45 | 9.89 | 10.28 | 10.51 | 10.70 | 10.81 | 10.95 | 11.64 | 12.66 | 12.40 | 12.30 | 12.14 | 11.82 |
| 9 | 9.92 | 10.54 | 11.05 | 11.57 | 11.94 | 12.19 | 12.35 | 12.53 | 13.32 | 14.49 | 14.21 | 14.09 | 13.90 | 13.58 |
| 10 | 10.77 | 11.49 | 12.21 | 12.86 | 13.33 | 13.67 | 13.88 | 14.11 | 15.01 | 16.33 | 16.04 | 15.90 | 15.69 | 15.31 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 16.035 |
| SC2 | 0 | 8 | 10.953 |
| SC3 | -18 | 7 | 8.992 |
| SC4 | -25 | 6 | 7.160 |
| SC5 | -34 | 6 | 6.828 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.